| 2008-06-19 14:59:30 | *****DENIED***** |
| | |
| | NOTE:THE LETTER RECEIVED FROM PERMIT ENGINEERING |
| | SEVICES INC REFERENCES THE AQUA MOTEL ADDRESSED IN LAKE |
| | WORTH, FLORIDA.PLEASE BE ADVISED THIS BUILDING IS IN |
| | THE JURISDICTION OF THE CITY OF WEST PALM BEACH. |
| | |
| | |
| | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE DAILY. |
| | |
| | 3.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE |
| | WITH ACCESS TO / EGRESS FROM OTHER GUEST ROOMS OF THE |
| | BUILDING. |
| | |
| | 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED IN GENERAL;IN PARTICULAR CHAPTER 29 - |
| | EXISTING HOTELS AND DORMITORIES. |
| | |
| | 5.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN |
| | TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 6.SHOW THE LOCATION OF THE SMOKE ALARM IN THIS GUEST |
| | ROOM.AN APPROVED SINGLE-STATION SMOKE ALARM SHALL BE |
| | INSTALLED IN GUEST ROOM AND EVERY LIVING AREA AND |
| | SLEEPING ROOM WITHIN A GUEST SUITE. |
| | |
| | 7.DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL |
| | HAVE NOT LESS THAN A 20-MINUTE FIRE-RATING. |
| | |
| | 8.DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL BE |
| | SELF-CLOSING AND SELF-LATCHING. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET |
| | EACH COMMENT WAS ADDRESSED |
| | |
| | |