Plan Review Notes
Plan Review Notes For Permit 08060347
Permit Number 08060347
Review Stop B
Sequence Number 1
Notes
Date Text
2008-06-23 10:36:22BUILDING PLAN REVIEW
 PERMIT: 08060347
 ADD: 7800 S. DIXIE HWY
 CONT: J. PALMER INC.
 TEL: (561)848-7114
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 6-23-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) PLEASE SUBMIT 2 COPIES OF PLANS, REPORTS, PRODUCT
 APPROVALS AND OR SUBMITTALS FOR REVIEW FOR PERMIT.
 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. INDICATE THE USE
 AND OCCUPANCY OF THE BUILDING PER CHAPTER 3 AND THE
 BUILDING CONSTRUCTION TYPE PER CHAPTER 6 AND TABLE
 503.
  
 4)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALLAFFIX THEIR OFFICIAL SEAL, SIGNATURE
 AND DATE TO SAID DRAWINGS AND SPECIFICATION PER 106.1
 FBC 2004, THE EXEMPTION FROM LICENSURE UNDER 481.229
 FLORIDA STATUTES DOES NOT EXEMPT THE DESIGNER
 RESPONSIBLE FOR THE DRAWINGS FROM SIGNING AND DATING
 SAID DRAWINGS.
  
 5)106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS.
  
 6)THE LETTER FROM PERMIT ENGINEERING SERVICES, INC.
 NEEDS TO SHOW THE CORRECT ADDRESS OF THE BUILDING. THE
 LETTER REFERS TO LAKE WORTH AS THE CITY. A PROFESSIONAL
 ENGINEER SHALL SIGN HIS NAME AND AFFIX HIS SEAL TO ALL
 PLANS, SPECIFICATIONS, REPORTS, FINAL BID DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE, OR
 OTHER DOCUMENTS PREPARED OR ISSUED BY SAID REGISTRANT
 AND BEING FILED FOR PUBLIC RECORD. IF PRACTICING
 THROUGH A DULY AUTHORIZED ENGINEERING BUSINESS, THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 SHALL BE INDICATED ON EACH SHEET. ALL THE INFORMATION
 IN THE LETTER FROM THE ENGINEERING FIRM SHALL BE SHOWN
 IN DETAIL ON ARCHITECTURAL PLANS.61G15-23.002
  
 7)A CERTIFIED ROOFING CONTRACTOR SHALL BE RESPONSIBLE
 FOR ALL ROOFING WORK.
 ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 _XX 1) CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY:
 MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF
 EACH ROOF TYPE
  
 _XX 2) FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE EVALUATION REPORT SUBMITTED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX 3) FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY
 YOU ARE USING.ALSO INDICATE WHICH FASTENER IF THE
 OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
  
 _XX 4) FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 _XX 5) SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING.
  
 8)106.3.3*THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. USING THE INFORMATION FROM THE
 PRODUCT APPROVALS, CIRCLE OR HI-LIGHT WHICH DOOR AND
 WINDOW WILL BE INSTALLED,
  
 9)STATE THE R-VALUE FOR THE INSULATION WHICH WILL BE
 INSTALLED IN THE ATTIC. 13-604.1
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]