| 2008-06-23 10:36:22 | BUILDING PLAN REVIEW |
| | PERMIT: 08060347 |
| | ADD: 7800 S. DIXIE HWY |
| | CONT: J. PALMER INC. |
| | TEL: (561)848-7114 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 6-23-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) PLEASE SUBMIT 2 COPIES OF PLANS, REPORTS, PRODUCT |
| | APPROVALS AND OR SUBMITTALS FOR REVIEW FOR PERMIT. |
| | 106.1* /2004 SUBMITTAL DOCUMENTS WEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 3)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. INDICATE THE USE |
| | AND OCCUPANCY OF THE BUILDING PER CHAPTER 3 AND THE |
| | BUILDING CONSTRUCTION TYPE PER CHAPTER 6 AND TABLE |
| | 503. |
| | |
| | 4)A DESIGN PROFESSIONAL THAT IS REGISTERED TO |
| | PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA |
| | STATUTES SHALLAFFIX THEIR OFFICIAL SEAL, SIGNATURE |
| | AND DATE TO SAID DRAWINGS AND SPECIFICATION PER 106.1 |
| | FBC 2004, THE EXEMPTION FROM LICENSURE UNDER 481.229 |
| | FLORIDA STATUTES DOES NOT EXEMPT THE DESIGNER |
| | RESPONSIBLE FOR THE DRAWINGS FROM SIGNING AND DATING |
| | SAID DRAWINGS. |
| | |
| | 5)106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS. |
| | |
| | 6)THE LETTER FROM PERMIT ENGINEERING SERVICES, INC. |
| | NEEDS TO SHOW THE CORRECT ADDRESS OF THE BUILDING. THE |
| | LETTER REFERS TO LAKE WORTH AS THE CITY. A PROFESSIONAL |
| | ENGINEER SHALL SIGN HIS NAME AND AFFIX HIS SEAL TO ALL |
| | PLANS, SPECIFICATIONS, REPORTS, FINAL BID DOCUMENTS |
| | PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE, OR |
| | OTHER DOCUMENTS PREPARED OR ISSUED BY SAID REGISTRANT |
| | AND BEING FILED FOR PUBLIC RECORD. IF PRACTICING |
| | THROUGH A DULY AUTHORIZED ENGINEERING BUSINESS, THE |
| | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | SHALL BE INDICATED ON EACH SHEET. ALL THE INFORMATION |
| | IN THE LETTER FROM THE ENGINEERING FIRM SHALL BE SHOWN |
| | IN DETAIL ON ARCHITECTURAL PLANS.61G15-23.002 |
| | |
| | 7)A CERTIFIED ROOFING CONTRACTOR SHALL BE RESPONSIBLE |
| | FOR ALL ROOFING WORK. |
| | ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | |
| | _XX 1) CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| | INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY: |
| | MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE / AREA OF |
| | EACH ROOF TYPE |
| | |
| | _XX 2) FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| | IN ADDITION TO THE EVALUATION REPORT SUBMITTED, |
| | FAC9B72.WWW.FLORIDABUILDING.ORG |
| | |
| | _XX 3) FOR THE FLAT DECK, SELECT THE APPROVED ASSEMBLY |
| | YOU ARE USING.ALSO INDICATE WHICH FASTENER IF THE |
| | OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS. |
| | |
| | _XX 4) FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES. |
| | |
| | _XX 5) SEE PRODUCT LIMITATION #7.CALCULATIONS |
| | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| | |
| | 8)106.3.3*THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. USING THE INFORMATION FROM THE |
| | PRODUCT APPROVALS, CIRCLE OR HI-LIGHT WHICH DOOR AND |
| | WINDOW WILL BE INSTALLED, |
| | |
| | 9)STATE THE R-VALUE FOR THE INSULATION WHICH WILL BE |
| | INSTALLED IN THE ATTIC. 13-604.1 |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |