| Date |
Text |
| 2008-06-18 11:12:24 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING W/2007 REVISIONS |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. PLANS ARE REQUIRED TO BE DRAWN/DESIGNED BY A DESIGN |
| | PROFESSIONAL, (ARCHITECT OR ENGINEER) PER FS 481.229(C) |
| | & SECTION 106.1. |
| | |
| | 2. SUBMIT AN EXISTING FLOOR PLAN SHOWING THE LOCATION |
| | OF THE BAR TO BE DEMO'D AND INDICATE WHICH PIPING SHALL |
| | BE DEMO'D TO DETERMINE THE SCOPE OF WORK. SECTION |
| | 106.1.2. |
| | |
| | 3. SUBMIT AN ISOMETRIC WATER RISER DIAGRAM AND AN |
| | ISOMETRIC SANITARY RISER DIAGRAM THAT REFLECTS THE |
| | FLOOR PALN. SECTION 106.3.5.1.3. FOR THE WATER RISER |
| | DIAGRAM SHOW ALL PIPE SIZES, VALVES & (WHERE REQUIRED |
| | BY SECTION 604.9) WATER HAMMER ARRESTORS. SECTION |
| | 601.1. FOR THE SANITARY RISER DIAGRAM SHOW ALL PIPE |
| | SIZES, VENTS, TRAPS ETC. SECTIONS 701.1, 710.1, 901.1 & |
| | 1001.1. APPROVED INDIRECT WASTE RECEPTORS ARE FLOOR |
| | SINKS OR HUB DRAINS PER SECTIONS 802.3 & 802.3.2. FLOOR |
| | DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. THE |
| | AIR GAPS SHALL COMPLY WITH SECTION 802.2.1. INDICATE |
| | THE CONNECTION LOCATION FOR THE WATER AND THE SANITARY |
| | SYSTEMS TO THE EXISTING SYSTEMS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |