Plan Review Notes
Plan Review Notes For Permit 08060343
Permit Number 08060343
Review Stop P
Sequence Number 1
Notes
Date Text
2008-06-18 11:12:24DENIED
 REFERENCE: FBC-2004 PLUMBING W/2007 REVISIONS
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS ARE REQUIRED TO BE DRAWN/DESIGNED BY A DESIGN
 PROFESSIONAL, (ARCHITECT OR ENGINEER) PER FS 481.229(C)
 & SECTION 106.1.
  
 2. SUBMIT AN EXISTING FLOOR PLAN SHOWING THE LOCATION
 OF THE BAR TO BE DEMO'D AND INDICATE WHICH PIPING SHALL
 BE DEMO'D TO DETERMINE THE SCOPE OF WORK. SECTION
 106.1.2.
  
 3. SUBMIT AN ISOMETRIC WATER RISER DIAGRAM AND AN
 ISOMETRIC SANITARY RISER DIAGRAM THAT REFLECTS THE
 FLOOR PALN. SECTION 106.3.5.1.3. FOR THE WATER RISER
 DIAGRAM SHOW ALL PIPE SIZES, VALVES & (WHERE REQUIRED
 BY SECTION 604.9) WATER HAMMER ARRESTORS. SECTION
 601.1. FOR THE SANITARY RISER DIAGRAM SHOW ALL PIPE
 SIZES, VENTS, TRAPS ETC. SECTIONS 701.1, 710.1, 901.1 &
 1001.1. APPROVED INDIRECT WASTE RECEPTORS ARE FLOOR
 SINKS OR HUB DRAINS PER SECTIONS 802.3 & 802.3.2. FLOOR
 DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. THE
 AIR GAPS SHALL COMPLY WITH SECTION 802.2.1. INDICATE
 THE CONNECTION LOCATION FOR THE WATER AND THE SANITARY
 SYSTEMS TO THE EXISTING SYSTEMS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  