2008-06-20 15:49:35BUILDING PLAN REVIEW
 PERMIT: 08060325
 ADD: 2777 MUSKEGON WAY
 CONT: VAN NESS & CALLAWAY CONST, INC.
 TEL: (561)278-0872
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)THE PRODUCT APPROVAL SUBMITTED IS FOR SHUTTER SPANS
 90? (7?-6?) OR LESS, SEE PAGES 8 AND 9.THE SHUTTER
 SCHEDULE INDICATES SPANS GREATER THAN 90? THEREFORE; A
 DIFFERENT PRODUCT APPROVAL SHALL BE SUBMITTED FOR THE
 SPANS GREATER THAN 90?.WHEN USING THE EDGE DISTANCE
 FACTORS THE ANCHOR SPACING WILL BE CLOSER ACCORDING TO
 THE FACTOR. PLEASE TAKE THIS INTO CONSIDERATION. IF
 SOME OF THE SHUTTERS SUBSTRATE WILL BE WOOD, INDICATE
 THE INFORMATION ON THE SHUTTER SCHEDULE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]