| 2008-06-20 15:49:35 | BUILDING PLAN REVIEW | | | PERMIT: 08060325 | | | ADD: 2777 MUSKEGON WAY | | | CONT: VAN NESS & CALLAWAY CONST, INC. | | | TEL: (561)278-0872 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1)THE PRODUCT APPROVAL SUBMITTED IS FOR SHUTTER SPANS | | | 90? (7?-6?) OR LESS, SEE PAGES 8 AND 9.THE SHUTTER | | | SCHEDULE INDICATES SPANS GREATER THAN 90? THEREFORE; A | | | DIFFERENT PRODUCT APPROVAL SHALL BE SUBMITTED FOR THE | | | SPANS GREATER THAN 90?.WHEN USING THE EDGE DISTANCE | | | FACTORS THE ANCHOR SPACING WILL BE CLOSER ACCORDING TO | | | THE FACTOR. PLEASE TAKE THIS INTO CONSIDERATION. IF | | | SOME OF THE SHUTTERS SUBSTRATE WILL BE WOOD, INDICATE | | | THE INFORMATION ON THE SHUTTER SCHEDULE. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|