| 2008-10-10 08:39:28 | ** DENIED 2ND REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #4. THE SAME |
| | COMMENT EXISTS. THE RESPONSE GOES INTO LENGTHY DETAIL |
| | ABOUT THE FPL TRANSFORMER AND SERVICE ENTRANCE |
| | CONDUCTORS. THE PREVIOUS COMMENT HAD NOTHING TO DO WITH |
| | THE FPL TRANSFORMER AS ALL WORK ON THE LINE SIDE AND |
| | MANY TIMES ON THE LOAD SIDE OF THEIR TRANSFORMER IS NOT |
| | UNDER THE RESPONSIBILITY OR JURISDICTION. IN FACT THE |
| | UTILITY WORK IS EXEMPT UNDER FEDERAL LAW. THE COMMENT |
| | HAD TO DO WITH THE ONLY TRANSFORMER ON RISER WHICH IS |
| | UNDER THE REVIEW OF THIS OFFICE. PLEASE SEE TRANSFORMER |
| | FED FROM PDP. THIS SHOWS 4-#6 CONDUCTORS AND THAT IS |
| | ALL. IS THE 4TH #6 A NEUTRAL WHICH WOULD NOT BE |
| | INSTALLED OR IS IT AN EQUIPMENT WHICH IS REQUIRED? |
| | 250.20,250.30,250.50,.250.110,250.50 ETC |
| | |
| | 2) NOTE: PLEASE REMOVE ANY REQUIREMENTS AND NOTES THAT |
| | LIGHTING DESIGN IS PER PALM BEACH COUNTY LIGHTING CODE. |
| | PALM BEACH COUNTY LIGHTING CODE/ORDINANCES IS NOT PART |
| | OF THE CITY OF WEST PALM BEACH. |
| | THE LIGHTING IS HOWEVER UNDER THE REVIEW OF FBC |
| | 13-415.2.ABC.1.3 FOR MAXIMUM ALLOWANCES PER THE FLORIDA |
| | ENERGY CODE. PLEASE BE SURE TO CHECK THE FEDERAL |
| | REQUIREMENTS UNDER THE ASHRAE STANDARDS OF 90.1 |
| | (SECTION 2.3) BEFORE A BUILDING MAY BE EXEMPT. ANY |
| | REQUIREMENTS OF A FEDERAL LEVEL ARE MORE RESTRICTIVE |
| | THAN STATE CODES AND APPLY. NO REQUEST WAS MADE FOR |
| | ENERGY CALCULATIONS FROM ELECTRICAL REVIEW OR OTHER |
| | REVIEW TRADES FOR THESE SPECIFIC ITEMS. PLEASE EXPLAIN |
| | WHY THE PACKAGE CONTAINS SECTIONS OF THE FLORIDA ENERGY |
| | CODE HIGH-LIGHTED AND RESPONSE MENTIONS THIS BUILDING |
| | IS EXEMPT? |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT WITH |
| | RESPECT TO GFI SHOWN ON GENERATOR. THE RESPONSE LETTER |
| | MENTIONS THIS IS FOR GROUND FAULT INDICATION AND TO SEE |
| | EXPLANATION/REVISED RISER. PLEASE EXPLAIN WHERE THIS |
| | STANDARD COMES FROM? THE STANDARD OF GFI IS FOR |
| | PERSONNEL PROTECTION AND EVEN WHEN REQUIRED SYSTEMS |
| | SUCH AS THOSE IN 240.12, 230.95 THESE ARE GFP WHICH IS |
| | NOT THE SAME. |
| | PLEASE REVISE RISER OR SYMBOLS TO ESTABLISH GROUND |
| | FAULT ALARM OR INDICATION. |
| | FBC 106.1.1 FOR CLARITY, COORDINATION AND ADDITIONAL |
| | INFORMATION. |
| | |
| | 4) NOTE: AS NOTED FOR INFORMATION THIS WILL BE PART OF |
| | BUILDING REVIEW: THE SUBMITTED WIND LOAD CALCULATIONS |
| | DO NOT CONTAIN AN ORIGINAL SIGNATURE AS REQUIRED PER FS |
| | 471.025. THIS SAME DESIGNER/ENGINEER HAS HAD THIS SAME |
| | COMMENT ON NUMEROUS OTHER PROJECTS. THIS OFFICE HAS |
| | PLACED A CALL TO SAID DESIGNER AND LEFT A MESSAGE TO |
| | CONTACT THIS OFFICE. |
| | THESE WILL BE RETAINED AND PLACED WITH OTHER PREVIOUSLY |
| | RETAINED DOCUMENTS FOR REVIEW FROM THE FLORIDA BOARD OF |
| | ENGINEERS. |
| | FAC 61G15-23.002, FS 4713025 |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS NOTE #8. RESPONSE MENTIONS |
| | DESIGN IS 480V 3-PHASE WITH GROUND AND THERE ARE NO 277 |
| | NEUTRAL LOADS. THIS REVIEWER IS CONFUSED AT THIS |
| | RESPONSE AS THE PREVIOUS COMMENT DID NOT STATE ANYTHING |
| | ABOUT A NEUTRAL WHICH IS A *GROUNDED CONDUCTOR*. THE |
| | PREVIOUS COMMENT STATED *EQUIPMENT * GROUNDING* |
| | CONDUCTORS MISSING FROM ATS TO GENERATOR, FIRST MEANS |
| | OF DISCONNECT TO THE ATS AND ATS TO THE PDP. THE |
| | RESPONSE MENTIONS NO NEUTRALS (GROUNDED CONDUCTORS) YET |
| | RISER SHOWS THEM???? |
| | 250.6, 250.24, 250.110, 250.122 ETC |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |