| 2008-07-11 10:58:51 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET S-1 AND S-2, ELECTRICAL BUILDING-FLOOR PLANS |
| | INDICATES 3 ALUMINUM SCUPPERS WITH DOWNSPOUTS AND SHEET |
| | S-6 INDICATES A SCUPPER AND CONDUCTOR HEAD- FRONT-SIDE |
| | DETAILS, HOWEVER THERE ARE NO SIZES OF THE SCUPPER, |
| | CONDUCTOR HEAD OR DOWNSPOUTS BEING INDICATED AS WELL AS |
| | THE REQUIRED SECONDARY ROOF DRAINAGE AND ROOF |
| | CALCULATION BEING INDICATED. PLEASE PROVIDE THE |
| | FOLLOWING INFORMATION PER THE FOLLOWING CODE |
| | REFERENCES. |
| | |
| | A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF |
| | AND VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS |
| | AND SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004 |
| | PLUMBING, SECTION 1106. |
| | |
| | B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004 |
| | PLUMBING, SECTION 1106.2 |
| | |
| | C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION |
| | 1106.4 |
| | |
| | D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING, |
| | SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004 |
| | PLUMBING, TABLE 1106.7. |
| | NOTE: THE SCUPPER DETAIL ON SHEET S-6 INDICATES THE |
| | SCUPPER 3/4" ABOVE THE ROOF. IS IT THE INTENT TO HAVE |
| | 3/4" OF WATER ON THE ROOF AS INDICATED? |
| | |
| | E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004 |
| | PLUMBING, SECTION 1107. |
| | A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING, |
| | SECTION 1107.1. |
| | B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING, |
| | SECTION 1107.2. |
| | |
| | 2. THERE ARE NO FLOOR DRAINS OR POTABLE WATER HOSE |
| | BIBBS BEING INDICATED ON THE PLANS. IS IT THE INTENT |
| | NOT TO HAVE THESE ITEMS OR IS THIS AN OVERSIGHT? |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |