| 2008-07-07 13:53:00 | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE VERIFY WHY THE GENERATOR IS SHOWING GFI |
| | PROTECTION. IT IS UNCLEAR AT THIS TIME WHY THIS TYPE PF |
| | PERSONNEL PROTECTION IS BEING PROVIDED ON THE GENERATOR |
| | BREAKER. |
| | ** CODE SECTIONS SUCH AS 240.13, 230.95 REQUIRED GROUND |
| | FAULT BUT NOT IN THIS CASE. |
| | |
| | 2)NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETSFOR THE NEW PROPOSED ATS AND GENERATOR. |
| | 90.7, 110.3, 702.6 |
| | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | CLARITY. |
| | |
| | 3) NOTE: PLEASE VERIFY THE NEW MAIN WHICH INDICATES A |
| | SHUNT TRIP BREAKER ACTUALLY STILL CONTAINS THE MANUAL |
| | MEANS OF DISCONNECT RATED FOR LOAD SERVED PER 230.76, |
| | 230.79 |
| | |
| | 4) NOTE: PLEASE VERIFY THE NUMBER OF CONDUCTORS ON THE |
| | LINE SIDE OF THE TRANSFORMER.IT APPEARS TO INDICATE A |
| | NEUTRAL AND NOT AN EQUIPMENT GROUND. |
| | PLEASE VERIFY THE CONDUCTORS ON THE LOAD SIDE OF THE |
| | TRANSFORMER ALSO. WILL THE EQUIPMENT GROUNDING |
| | CONDUCTOR BE THE SAME SIZE? |
| | 240.21, 310.16, 250.20 ETC |
| | |
| | 5) NOTE: PLEASE INDICATE THE ATTACHMENT LOCATION OF THE |
| | TRANSFORMER. ALONG WITH THE CONDUCTOR SIZE. 250.20, |
| | 250.50, 250.58, 25.66. |
| | |
| | 6) NOTE: THE PHOTO-METRICS NOTED ON E-1 STATE |
| | REQUIREMENTS PER PALM BEACH COUNTY. THIS PROJECT IS |
| | LOCATED WITH THE CITY OF WEST PALM BEACH. THE LIGHTING |
| | AS SHOWN IS NOT REQUIRED. |
| | PLEASE BE SURE TO ADJUST LOCATION. |
| | |
| | 7) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS AS FUEL |
| | TANKS/PLANS WILL BE REQUIRED TO BE STAMPED BY DERM. |
| | (DEPARTMENT OF ENVIRONMENTAL RESOURCE MANAGEMENT. |
| | |
| | 8) NOTE: PLEASE SEE RISER AS THE EQUIPMENT GROUNDING |
| | CONDUCTORS FROM MAIN TO ATS AND ATS TO DISTRIBUTION |
| | BOARD ARE MISSING. |
| | 250.110, 250.122 ETC |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |