Plan Review Notes For Permit 08060313
Permit Number 08060313
Review Stop B
Sequence Number 4
Notes
Date Text
2009-01-02 16:59:192004 FBC W/2007 REVISIONS
 CHLORINE STORAGE BUILDING
  
 DENIED BY BUILDING
  
 1) PLEASE SPECIFY THE TYPE OF CONSTRUCTION , OCCUPANCY
 AND SQUARE FOOTAGE OF THE EXISTING STRUCTURE ON THE
 PLANS. FBC 602 AND 302.1
  
 2) SPECIFY THE TYPE AND AMOUNT OF CHLORINE THAT WILL IN
 USE AND STORAGE WITHIN THE BUILDING. FBC SECTION 307.9
 CONTAINS EXCEPTIONS WHICH ALLOW STRUCTURES THAT DO NOT
 CONTAIN MORE THAN THE MAXIMUM ALLOWABLE QUANTITIES PER
 CONTROL AREA OF HAZARDOUS MATERIALS AS SHOWN IN TABLES
 307.7(1) AND (2) TO NOT BE CLASSIFIED AS GROUP H, BUT
 TO BE CLASSIFIED AS THE OCCUPANCY THEY MOST NEARLY
 RESEMBLE. BECAUSE THIS BUILDING DOES NOT MEET THE 50
 FOOT DISTANCE TO LOT LINES THAT IS REQUIRED FOR AN H-3
 OCCUPANCY BY FBC 415.3.1, CONTROL AREAS WILL BE
 REQUIRED. NOTE: TABLE 307.7(2) ALLOWS 810 CUBIC FEET OF
 GAS AGGREGATE QUANTITY IN USE AND STORAGE. THE QUANTITY
 CAN BE INCREASED 100 PER CENT WHEN STORED IN APPROVED
 STORAGE CABINETS, GAS CABINETS OR EXHAUSTED ENCLOSURES
 SEE FOOTNOTE F FOR TABLE 307.7(2).
  
 3) SPECIFY THE REQUIRED FIRE RATING OF THE WALLS AND
 CEILING OF THE CHLORINE ROOM (SEE FBC 414.2 CONTROL
 AREA). FBC 414.2.1 REQUIRES ONE HOUR FIRE RATED WALLS
 AND CEILING.
  
 4) INDICATE THE LOCATIONS AND AMOUNT OF CHLORINE THAT
 WILL BE STORED IN EACH CONTROL AREA. FBC 414.1.3 AND
 TABLE 414.2.2
  
 5) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR EXHAUST VENT. FAC RULE 9B-72
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]