| Date |
Text |
| 2009-01-02 16:59:19 | 2004 FBC W/2007 REVISIONS |
| | CHLORINE STORAGE BUILDING |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) PLEASE SPECIFY THE TYPE OF CONSTRUCTION , OCCUPANCY |
| | AND SQUARE FOOTAGE OF THE EXISTING STRUCTURE ON THE |
| | PLANS. FBC 602 AND 302.1 |
| | |
| | 2) SPECIFY THE TYPE AND AMOUNT OF CHLORINE THAT WILL IN |
| | USE AND STORAGE WITHIN THE BUILDING. FBC SECTION 307.9 |
| | CONTAINS EXCEPTIONS WHICH ALLOW STRUCTURES THAT DO NOT |
| | CONTAIN MORE THAN THE MAXIMUM ALLOWABLE QUANTITIES PER |
| | CONTROL AREA OF HAZARDOUS MATERIALS AS SHOWN IN TABLES |
| | 307.7(1) AND (2) TO NOT BE CLASSIFIED AS GROUP H, BUT |
| | TO BE CLASSIFIED AS THE OCCUPANCY THEY MOST NEARLY |
| | RESEMBLE. BECAUSE THIS BUILDING DOES NOT MEET THE 50 |
| | FOOT DISTANCE TO LOT LINES THAT IS REQUIRED FOR AN H-3 |
| | OCCUPANCY BY FBC 415.3.1, CONTROL AREAS WILL BE |
| | REQUIRED. NOTE: TABLE 307.7(2) ALLOWS 810 CUBIC FEET OF |
| | GAS AGGREGATE QUANTITY IN USE AND STORAGE. THE QUANTITY |
| | CAN BE INCREASED 100 PER CENT WHEN STORED IN APPROVED |
| | STORAGE CABINETS, GAS CABINETS OR EXHAUSTED ENCLOSURES |
| | SEE FOOTNOTE F FOR TABLE 307.7(2). |
| | |
| | 3) SPECIFY THE REQUIRED FIRE RATING OF THE WALLS AND |
| | CEILING OF THE CHLORINE ROOM (SEE FBC 414.2 CONTROL |
| | AREA). FBC 414.2.1 REQUIRES ONE HOUR FIRE RATED WALLS |
| | AND CEILING. |
| | |
| | 4) INDICATE THE LOCATIONS AND AMOUNT OF CHLORINE THAT |
| | WILL BE STORED IN EACH CONTROL AREA. FBC 414.1.3 AND |
| | TABLE 414.2.2 |
| | |
| | 5) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR EXHAUST VENT. FAC RULE 9B-72 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |