| 2008-10-14 16:56:44 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS |
| | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | |
| | 1} INDICATE HOW THE BUILDING IS BEING FED AND FROM |
| | WHERE. FEEDER SIZES AND OCP ARE REQUIRED FOR |
| | REVIEW.215.5 NEC*** A RISER DIAGRAM IS REQUIRED PER |
| | THIS ARTICLE TO COMPLY WITH THIS COMMENT.. |
| | |
| | 2} 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) |
| | OR BRANCH CIRCUIT(S) |
| | (A) GROUNDING ELECTRODE BUILDING(S) OR STRUCTURE(S) |
| | SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A |
| | GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM |
| | INSTALLED IN ACCORDANCE WITH 250.50. THE GROUNDING |
| | ELECTRODE CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE |
| | WITH 250.32(B) OR (C). WHERE THERE IS NO EXISTING |
| | GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S) |
| | REQUIRED IN 250.50 SHALL BE INSTALLED.*** THIS COMMENT |
| | CAN ALSO BE RESPONDED TO WITH A RISER DIAGRAM, BUT |
| | CANNOT BE A RESPONSE ON THE COMMENT SHEET (WHICH IS NOT |
| | PRINTED OUT CORRECTLY, SEE COMMENT #2 ON THE RES SHEET |
| | AND COMMENT #2 ON THE ORIGINAL COMMENT SHEET) THE RISER |
| | DIAGRAM MUST BE DRAWN AND SUBMITTED AS PART OF THE |
| | CONSTRUCTION DOCUMENTS. THE ELECTRICAL CONTRACTOR MAY |
| | DRAW THESE UNDER THE EXEMPTIONS OF FS 471.. |
| | |
| | 3} NEW COMMENT THAT WAS NOT MADE IN THE PREVIOUS |
| | REVIEW.***THE ENGINEER WHOSE NAME APPEARS ON THE TITLE |
| | BLOCK MUST SIGN, DATE AND SEAL THE DOCUMENT. |
| | 61G15-23.002 FAC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |