Plan Review Notes
Plan Review Notes For Permit 08060313
Permit Number 08060313
Review Stop P
Sequence Number 1
Notes
Date Text
2008-07-11 12:01:03PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 1 INDICATES A 4 INCH (4") FLOOR DRAIN. THE
 FOLLOWING IS REQUIRED FOR THE 4" FLOOR DRAIN PER
 (W.P.B. AS AMENDED) CHAPTER 1, SECTION 106.3.5.1.3
 COMMERCIAL PLUMBING (4)(6)(13), PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS OF THE FLOOR DRAIN.
 NOTE: WHERE A TRAP SEAL IS SUBJECT TO LOSS BY
 EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. A TRAP SEAL PRIMER VALVE SHALL CONFORM TO
 ASSA 1018 OR ASSE 1044. CLEARLY INDICATE THE TRAP SEAL
 PRIMER VALVE ON THE RESUBMITTED PLANS. PER FBC-
 PLUMBING SECTION 1002.4 TRAP SEALS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  