| 2008-07-11 12:01:03 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET 1 INDICATES A 4 INCH (4") FLOOR DRAIN. THE |
| | FOLLOWING IS REQUIRED FOR THE 4" FLOOR DRAIN PER |
| | (W.P.B. AS AMENDED) CHAPTER 1, SECTION 106.3.5.1.3 |
| | COMMERCIAL PLUMBING (4)(6)(13), PLEASE SUBMIT A |
| | PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING |
| | ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT |
| | LOCATIONS OF THE FLOOR DRAIN. |
| | NOTE: WHERE A TRAP SEAL IS SUBJECT TO LOSS BY |
| | EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE |
| | INSTALLED. A TRAP SEAL PRIMER VALVE SHALL CONFORM TO |
| | ASSA 1018 OR ASSE 1044. CLEARLY INDICATE THE TRAP SEAL |
| | PRIMER VALVE ON THE RESUBMITTED PLANS. PER FBC- |
| | PLUMBING SECTION 1002.4 TRAP SEALS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |