| Plan Review Notes For Permit 08060313 |
| Permit Number |
08060313 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-16 11:58:40 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS | | | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | | | | 1} INDICATE HOW THE BIULDING IS BEING FED AND FROM | | | WHERE.FEEDER SIIZES AND OCP ARE REQUIRED FOR | | | REVIEW.215.5 NEC. | | | | | | 2} 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S) | | | OR BRANCH CIRCUIT(S) | | | (A) GROUNDING ELECTRODE BUILDING(S) OR STRUCTURE(S) | | | SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A | | | GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM | | | INSTALLED IN ACCORDANCE WITH 250.50. THE GROUNDING | | | ELECTRODE CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE | | | WITH 250.32(B) OR (C). WHERE THERE IS NO EXISTING | | | GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S) | | | REQUIRED IN 250.50 SHALL BE INSTALLED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|