2008-06-16 11:58:40 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS
 AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} INDICATE HOW THE BIULDING IS BEING FED AND FROM
 WHERE.FEEDER SIIZES AND OCP ARE REQUIRED FOR
 REVIEW.215.5 NEC.
  
 2} 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY FEEDER(S)
 OR BRANCH CIRCUIT(S)
 (A) GROUNDING ELECTRODE BUILDING(S) OR STRUCTURE(S)
 SUPPLIED BY FEEDER(S) OR BRANCH CIRCUIT(S) SHALL HAVE A
 GROUNDING ELECTRODE OR GROUNDING ELECTRODE SYSTEM
 INSTALLED IN ACCORDANCE WITH 250.50. THE GROUNDING
 ELECTRODE CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE
 WITH 250.32(B) OR (C). WHERE THERE IS NO EXISTING
 GROUNDING ELECTRODE, THE GROUNDING ELECTRODE(S)
 REQUIRED IN 250.50 SHALL BE INSTALLED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  