| 2008-07-02 13:59:46 | 2004 FBC W/2007 REVISIONS |
| | INSTALL FIBERGLASS STRUCTURE |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE ENGINEER FOR SHELTER WORKS IS USING AN EMBOSSED |
| | SEAL THAT IS NO LONGER ACCEPTABLE AS OF JANUARY 1, |
| | 2006. SEE FAC 61G15-23.001 AND F.S.471.025. |
| | |
| | 2) ENGINEER IS REQUIRED TO LEGIBLY INDICATE THEIR NAME, |
| | ADDRESS AND LICENSE NUMBER ON EACH SHEET. SEE FAC |
| | 61G15-23.002. |
| | |
| | 3) THE WRONG CODES ARE SPECIFIED ON THE PLANS AND |
| | CALCULATIONS. THE CODE CURRENTLY IN EFFECT IS THE 2004 |
| | FBC W/2007 REVISIONS. |
| | |
| | 4) THE CALCULATIONS REFERENCE THE WRONG EDITIONS OF |
| | FBC, ASCE7 AND ACI 318. THE 2004 FBC REFERENCES |
| | ASCE7-02 AND ACI 318-02. PLEASE REVISE. |
| | |
| | 5) GENERAL NOTE #2 ON SHEET 1 OF PLANS SPECIFIES THAT A |
| | MINIMUM SEPARATION DISTANCE OF 10 FEET IS REQUIRED FROM |
| | THE NEAREST BUILDING. THE SITE PLAN DOES NOT COMPLY. |
| | |
| | 6) SPECIFY THE SIZE AND LENGTH/EMBED DEPTH OF THE |
| | EXPANSION ANCHORS @ 6" OC ON SHEET 4 OF THE PLANS. THE |
| | CALCULATIONS SPECIFY 3/8" DIAMETER ANCHOR BOLTS WITH |
| | 1-1/2" EMBEDMENT SPACED 12" OC. SEE CALCULATION SHEET 7 |
| | OF 13. |
| | |
| | 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR DOOR AS REQUIRED BY DCA RULE 9B-72. |
| | |
| | 8) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9) FBC TABLE 602 REQUIRES TWO HOUR FIRE RATED WALLS FOR |
| | A BUILDING OF TYPE V-B CONSTRUCTION AND F-1 OCCUPANCY |
| | AND A FIRE SEPARATION DISTANCE OF LESS THAN 5' . NOTE: |
| | SEE 702.1 DEFINITIONS. FIRE SEPARATION DISTANCE. THE |
| | DISTANCE MEASURED FROM THE BUILDING FACE TO THE CLOSEST |
| | INTERIOR LOT LINE, TO THE CENTERLINE OF A STREET, ALLEY |
| | OR PUBLIC WAY, OR TO AN IMAGINARY LINE BETWEEN TWO |
| | BUILDINGS ON THE LOT. THE DISTANCE SHALL BE MEASURED AT |
| | RIGHT ANGLES FROM THE FACE OF THE WALL. |
| | |
| | 10) SPECIFY THE OCCUPANCY, CONSTRUCTION TYPE AND AREA |
| | OF WALL OPENINGS FOR THE ADJACENT BUILDING IN ORDER TO |
| | DETERMINE COMPLIANCE WITH FIRE SEPARATION REQUIREMENTS. |
| | FBC 702. |
| | |
| | 11) THE MAXIMUM AREA OF WALL OPENINGS IN BOTH BUILDINGS |
| | IS REQUIRED TO COMPLY WITH FBC TABLE 704.8. NO OPENINGS |
| | ARE PERMITTED FOR A FIRE SEPARATION DISTANCE OF 0-3 |
| | FEET. |
| | |
| | 12) FBC 503.1.3 PERMITS TWO BUILDINGS ON THE SAME LOT |
| | TO BE CONSIDERED AS PORTIONS OF ONE BUILDING IF CERTAIN |
| | CONDITIONS ARE MET. SEE FBC 503.1.3 BUILDINGS ON SAME |
| | LOT. |
| | TWO OR MORE BUILDINGS ON THE SAME LOT SHALL BE |
| | REGULATED AS SEPARATE BUILDINGS OR SHALL BE CONSIDERED |
| | AS PORTIONS OF ONE BUILDING IF THE HEIGHT OF EACH |
| | BUILDING AND THE AGGREGATE AREA OF BUILDINGS ARE WITHIN |
| | THE LIMITATIONS OF TABLE 503 AS MODIFIED BY SECTIONS |
| | 504 AND 506 . THE PROVISIONS OF THIS CODE APPLICABLE TO |
| | THE AGGREGATE BUILDING SHALL BE APPLICABLE TO EACH |
| | BUILDING. IF YOU CHOOSE TO DO THIS SHOW HOW THE TWO |
| | BUILDINGS WILL COMPLY. |
| | |
| | 13) SPECIFY THE TYPE (LIQUID OR GAS) AND AMOUNT OF |
| | CHLORINE THAT WILL BE STORED IN THE BUILDING. SUBMIT |
| | MATERIAL SAFETY DATA SHEETS FOR THE PRODUCT.THIS |
| | INFORMATION TO BE USED TO DETERMINE IF THE OCCUPANCY |
| | WILL BE DETERMINED AS HIGH HAZARD GROUP H. SEE FBC |
| | 307. |
| | |