2008-07-17 09:40:501. THE HYDRAULIC CALCULATIONS INDICATES 2 1/2 HOSE
 VALVES BUT THE PLANS ILLUSTRATE 1 1/2 HOSE VALVES FOR
 THE STANDPIPE SYSTEMS.. 2 1/2 HOSE VALVES SHALL BE
 PROVIDED AT EACH FLOOR. 2 1/2 TO 1 1/2 REDUCERS ALSO
 NEED TO BE AT EACH HOSE VALVE.
  
  
 APPROVED PROVISO
  