| 2008-07-15 16:45:29 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | FROM PREVIOUS LIST: | | | | | | 1.SEE SHEET 5.CONNECTIN TYPE A REQUIRES 9" SPACING | | | WITH A FACTOR OF .86 FOR A 3" EDGE DISTANCE.12" | | | SPECIFIED ON THE INSTALLATION SCHEDULE, OPENINGS 6 AND | | | 7.NOTE THAT YOU HAVE CIRCLED THIS ON THE PRODUCT | | | APPROVAL (9" SPACING) BUT DID NOT USE THIS NUMBER ON | | | THE INSTALLATION SCHEDULE.CHECK ALL. | | | | | | 2ND REVIEW, THE INSTALLATION SCHEDULE WAS REVISED TO | | | 9".SEE FIRST LIST; A 3" EDGE DISTANCE REQUIRES A | | | FACTOR OF .86, SEE PAGE 5.YOU HAVE CIRCLED THIS | | | ALREADY ON THE PRODUCT APPROVAL, BUT DID NOT APPLY THE | | | FACTOR TO THE ANCHOR SPACING.PLEASE REVISE THE | | | INSTALLATION SCHEDULE AND CHECK ALL OTHER OPENINGS. | | | | | | 3RD REVIEW, INSTALLATION SCHEDULE FOR OPENINGS 6, 7 NOW | | | SPECIFIES 8".A 9" ANCHOR SPACING TIMES A FACTOR OF | | | .86 EQUALS 7.74. | | | | | | NEW COMMENT: | | | | | | ONLY ONE ACCORDION PRODUCT APPROVAL SUBMITTED.TWO | | | COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED FOR PERMIT | | | ISSUANCE. | | | |
|