| 2008-06-30 16:56:45 | BUILDING PLAN REVIEW |
| | PERMIT: 08060213 |
| | ADD: 1401 NORTHPOINTE PARKWAY SUITE # |
| | CONT: CARRICK |
| | TEL: (561)718-9090 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS, |
| | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR |
| | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL |
| | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A |
| | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN |
| | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED |
| | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS |
| | WEST PALM BEACH ADMINISTRATIVE CODE. |
| | |
| | 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE |
| | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO |
| | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION |
| | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE |
| | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR |
| | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) INFORMATIONAL FL S S 713.13NOTICE OF |
| | COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| | VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST |
| | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO |
| | THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS. |
| | |
| | 2) THE INFORMATION REQUESTED BELOW WILL PROVIDE FOR AN |
| | ACCURATE REVIEW OF YOUR PROJECT AND CREATE LESS |
| | QUESTIONS IN REGARDS TO THE TYPE OF CONSTRUCTION. |
| | 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT |
| | IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, |
| | TABLE 601. |
| | D) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED E) |
| | WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | F ) NUMBER OF FLOORS |
| | |
| | 3) SEE ATTACHED AREIAL, IT APPEARS THIS BUILDING COVERS |
| | THREE INDIVDUAL LOTS, LOT NUMBER 0251, 0252 AND 0242. |
| | UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE |
| | TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS |
| | WHICH COMBINE TO FORM 'THE SITE'.A 'UNITY OF TITLE' |
| | SHALL BE RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A |
| | COPY OF THE RECORDED 'UNITY OF OF TITLE' DOCUMENT SO |
| | THAT FBC TABLE 601 BOUNDARY LINE REQUIREMENTS MAY BE |
| | DEEMED NOT APPLICABLE. FORMS ARE AVALIBLE AT CITY HALL |
| | 5TH FLOOR ZONING DEPARTMENT. |
| | |
| | 4) OFFICE 100A NORTH WALL IS THE COMMON WALL TO THE |
| | STAIRWELL AND EXIT PASSAGEWAY THIS WALL IS NOT |
| | DESIGNATED AS A RATED WALLPLEASE SEE 707.4. |
| | |
| | 5)IT ROOM # 107 IF THIS ROOM IS CONSIDERED A TRUE IT |
| | ROOM, THEN THE WALLS WILL NEED TO BE RATED SEE NEC |
| | 645.2, ALSO SEE ELECTRICAL COMMENTS. |
| | |
| | 6)LS1 THE PLAN INDICATES A NEW EXIT LIGHT IN THE |
| | WAREHOUSE AT DOOR# 5 VESTIBULE, BUT THE SIGHT LINE IS |
| | BLOCKED FROM THE IT ROOM. SEE 1006.3.1 EXIT LIGHTS |
| | SHALL BE MARKED AND READILY VISIBLE FROM ANY DIRECTION |
| | OF EXIT ACCESS. PLEASE CORRECT OR ADJUST FIXTURES. |
| | |
| | 7) LS1 PLANAS ALSO INDICATE A NEW EXIT LIGHT AT DOOR# |
| | 14 LEAVING THE BUSSINESS OCCUPANCY IN TO THE WAREHOUSE |
| | OCCUPANCY, THE EXISTING BUILDING CODE TABLE 812.4.1 |
| | HAZARD CATEGORIES INDICATES BUSINESSAND S1 OCCUPANCY |
| | ARE OF THE SAME HAZARD CATEGORY ALLOWING EXITING |
| | THROUGH THE WAREHOUSE. PLEASE PROVIDE A EGRESS PATH FOR |
| | THE WAREHOUSE AREA.PLANS INDICATE A FENCED IN AREA AND |
| | GATE TO THE EGRESS DOOR. FORTHIS DOOR TO BE USED AS A |
| | MEANS OF EGRESS THIS GATE CAN NOT BE |
| | LOCKED.1013.2.ADDITIONAL EXIT LIGHTS MAY BE REQUIRED IN |
| | THE WAREHOUSE AREA DUE TO RACK STORAGE.1006.3.1. |
| | |
| | 8) LS1 AND A-3 BOTH INDICATE IN HALL 127 CONSIDERED A |
| | EXIT PASSAGEWAY A FIRE EXTINGHISHER PLEASE PROVIDE |
| | ADDTIONAL INFORMATION ON THE DIMENSIONS OF THIS UNIT. |
| | 1003.3.3 HORIZONTAL PROJECTIONS. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |