| 2008-06-30 15:25:42 | 2004 FBC W/2007 REVISIONS | | | GARAGE ADDITION | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL | | | BE REQUIRED. | | | | | | 2) ON SHEET 4.0 SPECIFY 8D RING SHANK NAILS FOR THE | | | ROOF SHEATHING FASTENING AS REQUIRED BY FBC R 803.2.1. | | | | | | 3) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | | | | 4) THE PRODUCT APPROVAL FOR THE HARDIPLANK SIDING | | | REQUIRES 5/8" PLYWOOD WALL SHEATHING AND 1/2" IS | | | SPECIFIED ON THE WALL SECTION ON 3.0. PLEASE REVISE. | | | DCA RULE 9B-72 | | | | | | 5) SPECIFY WHICH ONE OF THE ATTACHMENT METHODS LISTED | | | IN THE TABLES OF THE ROOF TILE PRODUCT APPROVAL WILL BE | | | USED TO INSTALL THEM. FBC R905.3.7 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|