2008-07-23 16:07:33RESIDENTIAL (R3)ENTRY DOORBUILDING REVIEW THIRD
 CHECKLIST.
 REVIEW UNDER FBC 2004.
  
 1- FLORIDA PRODUCT APPROVAL FL10989SUBMITTED IS FOR
 CODE VERSION 2007. FBC 2007 IS NOT THE CURRENT
 ADOPTED CODE.HOUSE WAS PERMITTED UNDER FBC 2004 CODE
 VERSION.NEED TO PROVIDE PRODUCT APPROVAL FOR 2004
 CODE VERSION TO MATCH CODE VERSION OF THE HOUSE. AS AN
 ALTERNATIVE APPLICATION FOR LOCALPRODUCT APPROVAL
 MAY BE SUBMITTED. SEE ATTACHED COPY OF LOCAL PRODUCT
 APPROVAL FORM.PROVIDE 3 COMPLETEFORMS AND 3
 COMPLETE SETS OF ENGINEER'S REPORTSAND DRAWINGS WITH
 ORIGINAL SEAL AND SIGNATURE.ENGINEER'S REPORT AND
 DRAWINGS NEED TOREFERENCE CURRENT CODE VERSION FBC
 2004, NOT FBC 2007.THERE ARE NO FEES FOR LOCAL
 PRODUCT APPROVAL, BUT THEY NEED TO BE APPROVED BY THE
 BUILDING OFFICIAL.
  
 2- RE-SUBMITTAL FEES WILL APPLY.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712