| 2008-07-02 11:07:55 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.SEE OPENING 8.A 2" EDGE DISTANCE REQUIRES A |
| | FACTOR OF .50, SEE SHEET 5 (9" SPACING TIMES .5 WOULD |
| | REQUIRE A MAXIMUM OF 4.5" SPACING). |
| | |
| | 2.IT IS ACCEPTABLE TO EXCEED CODE COMPLIANCE. |
| | HOWEVER, PLEASE CLARIFY WHY 4", 4 1/2", AND 8" ARE |
| | SPECIFIED FOR BOTTOM ANCHOR SPACING BUT THE CONDITIONS |
| | ARE THE SAME AS THE TOP WHICH SPECIFIES 9".THIS IS |
| | ACCEPTABLE; YOU CAN ALWAYS DECREASE ANCHOR SPACING |
| | PROVIDED IT MEETS THE MINIMUM SPACING.HOWEVER, PLEASE |
| | CONFIRM THAT ALL OTHER INFORMATION IS CORRECT AND IF |
| | POSSIBLE CLARIFY.PLEASE NOTE THAT THE PLAN REVIEW |
| | WOULD NOT FAIL FOR THIS REASON. |
| | |
| | 3.I ATTEMPTED TO GET THIS RESOLVED ON THE TELEPHONE; |
| | PLEASE NOTE THAT YOUR SERVICE WOULD NOT ALLOW A |
| | LENGTHY.I WAS HOPING TO LEAVE A DETAILED MESSAGE BUT |
| | WAS CUT OFF.PLEASE ADDRESS COMMENTS (REVISE THE |
| | INSTALLATION SCHEDULE) AND RESUBMIT. |