2008-07-02 11:07:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.SEE OPENING 8.A 2" EDGE DISTANCE REQUIRES A
 FACTOR OF .50, SEE SHEET 5 (9" SPACING TIMES .5 WOULD
 REQUIRE A MAXIMUM OF 4.5" SPACING).
  
 2.IT IS ACCEPTABLE TO EXCEED CODE COMPLIANCE.
 HOWEVER, PLEASE CLARIFY WHY 4", 4 1/2", AND 8" ARE
 SPECIFIED FOR BOTTOM ANCHOR SPACING BUT THE CONDITIONS
 ARE THE SAME AS THE TOP WHICH SPECIFIES 9".THIS IS
 ACCEPTABLE; YOU CAN ALWAYS DECREASE ANCHOR SPACING
 PROVIDED IT MEETS THE MINIMUM SPACING.HOWEVER, PLEASE
 CONFIRM THAT ALL OTHER INFORMATION IS CORRECT AND IF
 POSSIBLE CLARIFY.PLEASE NOTE THAT THE PLAN REVIEW
 WOULD NOT FAIL FOR THIS REASON.
  
 3.I ATTEMPTED TO GET THIS RESOLVED ON THE TELEPHONE;
 PLEASE NOTE THAT YOUR SERVICE WOULD NOT ALLOW A
 LENGTHY.I WAS HOPING TO LEAVE A DETAILED MESSAGE BUT
 WAS CUT OFF.PLEASE ADDRESS COMMENTS (REVISE THE
 INSTALLATION SCHEDULE) AND RESUBMIT.