| Plan Review Notes For Permit 08060178 |
| Permit Number |
08060178 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-11-26 14:11:06 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- REVISE ENERGY CALCULATIONS: | | | A) THIS IS NOT NEW CONSTRUCTION. THIS IS AN EXISTING | | | APARTMENT. | | | B) SPECIFY NUMBER OF UNITS. THIS IS A MULTIFAMILY | | | PROJECT. | | | C) GLASS AREA ON ITEM 7A TO MATCH WITH 7B. | | | D) INCLUDE COMMON WALLS AREA AND INSULATION AS REQUIRED | | | BY SEC. 13-602.1.ABC.1.1 FBC 2004. | | | E) INCLUDE COMMON CEILINGS/FLOORS AREAS AND INSULATION | | | AS REQUIRED BY SEC. 13-304.1.ABC.1.2 FBC 2004. | | | F) TOTAL CEILING TYPES TO MATCH CONDITIONED FLOOR AREA | | | ON ITEM #6. COORDINATE WITH ITEM # 1E ABOVE. | | | ***NOTE: REVISION FEES WILL APPLY. | | | | | | 2- PROVIDE PRODUCT APPROVAL FOR OUTSWING ENTRY DOOR AS | | | SHOWN ON PLANS. INFORMATION SUBMITTED IS FOR INSWING | | | DOORS. | | | NOTE: ARCHITECT TO REVIEW AN APPROVE IN WRITING ALL | | | PRODUCT APPROVALS PRIOR TO SUBMITTAL TO THIS OFFICE. | | | | | | 3- MIN. R11 INSULATION REQUIRED ON CEILING/FLOOR AS | | | REQUIRED BY SEC. 13-604.1.ABC.1.2 FBC 2004. | | | |
|