| 2008-11-07 17:00:57 | RESIDENTIAL (R2) REHABILITATION, BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- REVISE ENERGY CALCULATIONS SUBMITTED: |
| | A) THIS IS NOT AN ADDITION. THIS IS AN EXISTING UNIT |
| | THAT IS GOING TO BE REHABILITATED BECAUSE OF FIRE |
| | DAMAGE. |
| | B) ITEM #7A AND #7B DON'T MATCH INFORMATION SHOWN ON |
| | ARCHITECTURAL PLANS. REVISE AS REQUIRED. |
| | C) SQUARE FOOTAGE OF GLASS ON PAGE TWO DOESN'T MATCH |
| | ACTUAL WINDOWS SHOWN ON ARCHITECTURAL PLANS. REVISE AS |
| | REQUIRED. |
| | ALSO, REVISE ORIENTATION OF WINDOWS. NOT ALL WINDOWS |
| | ARE LOCATED ON THE WEST SIDE. SEE PLANS AND REVISE AS |
| | REQUIRED. |
| | D) REVISE CEILING TYPE ITEM #10A. THERE IS NO ATTIC. |
| | THERE IS ANOTHER APARTMENT ON TOP OF THIS UNIT. REVISE |
| | AS REQUIRED. |
| | E) CLARIFY HOW GETTING R-4 INSULATION ON SLAB ON GRADE. |
| | REVISE AS REQUIRED. SEE PLANS. |
| | F) REVISE WALL TYPES ON ITEM #9. SEE PLANS AND REVISE |
| | AS REQUIRED. PLANS SHOW WOOD FRAMING CONSTRUCTION, NOT |
| | CONCRETE. |
| | |
| | 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE SUBMITTED LATER AT TIME OF PERMIT |
| | PICK UP. |
| | |
| | 3- ENGINEER NEEDS TO PROVIDE THE ENGINEERING FIRM |
| | MILTON ENGINEERING CONSULTANTS, P.A. CERTIFICATE OF |
| | AUTHORIZATION NUMBER ON ALL DRAWINGS AS REQUIRED BY |
| | SEC. 61G15--23.002(2) OF FLORIDA ADMINISTRATIVE CODE |
| | AND CHAPTER 471 FLORIDA STATUTE. (REPEAT COMMENT). |
| | |
| | 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED DCA |
| | RULE 9B-72 FOR: |
| | A) ENTRY DOOR AS SHOWN ON PLANS. NONE SUBMITTED. |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | PAGE AND PAGE SHOWING THE CONNECTOR. NO NEED TO SUBMIT |
| | COMPLETE REPORT. THIS APPLIES TO CONNECTORS ONLY. OTHER |
| | PRODUCT APPROVALS NEED TO SUBMIT COMPLETE REPORT. |
| | |
| | 5- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND |
| | APPROVED IN WRITING (NOT SIGNING AND SEALING) BY THE |
| | DESIGNER OF RECORD AS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. (REPEAT COMMENT). |
| | |
| | 6- DESIGNER OF RECORD TO SPECIFY LEVEL OF ALTERATION |
| | FOR THIS PROJECT AS REQUIRED BY SEC. 301.5 OF 2004 |
| | FLORIDA EXISTING BUILDING CODE. (REPEAT COMMENT). |
| | |
| | 7- SCOPE OF WORK SPECIFIED ON PERMIT APPLICATION IS FOR |
| | REPLACEMENT OF INTERIOR DRYWALL, CABINETS AND OTHER |
| | INTERIOR FINISHES ONLY. ELECTRICAL AND PLUMBING |
| | FIXTURES WERE CROSSED OUT. PLANS SUBMITTED ARE FOR NEW |
| | WINDOWS AND WINDOW FRAMING AND FOR COMPLETE RENOVATION |
| | OF APARTMENT. CLARIFY SCOPE OF WORK ON PERMIT |
| | APPLICATION AND REVISE TOTAL VALUATION DECLARED TO |
| | REFLECT ALL WORK TO BE PERFORMED. SEC. 108.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 8- ARCHITECT NEEDS TO DATE PLANS WHEN THEY WERE SEALED |
| | AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA |
| | ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE. |
| | |
| | 9- ARCHITECT TO SPECIFY ON DRAWINGS IF FLOOR/CEILING |
| | ASSEMBLY IS GOING TO BE REPLACED. COMPLY WITH SEC. 503 |
| | OF 2004 FLORIDA EXISTING BUILDING CODE. |
| | ***NOTE: UL SYSTEM L528 INCLUDES 16 FLOOR SYSTEMS. |
| | CLEARLY IDENTIFY WHICH FLOOR SYSTEM IS GOING TO BE |
| | INSTALLED. SEE L528 FOR DIFFERENT APPROVED SYSTEMS AND |
| | SELECT ONE. |
| | |
| | 10- CONTRACTOR NEEDS TO UPDATE INSURANCE INFORMATION |
| | WITH PERMIT CLERK. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |