2008-11-07 17:00:57RESIDENTIAL (R2) REHABILITATION, BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- REVISE ENERGY CALCULATIONS SUBMITTED:
 A) THIS IS NOT AN ADDITION. THIS IS AN EXISTING UNIT
 THAT IS GOING TO BE REHABILITATED BECAUSE OF FIRE
 DAMAGE.
 B) ITEM #7A AND #7B DON'T MATCH INFORMATION SHOWN ON
 ARCHITECTURAL PLANS. REVISE AS REQUIRED.
 C) SQUARE FOOTAGE OF GLASS ON PAGE TWO DOESN'T MATCH
 ACTUAL WINDOWS SHOWN ON ARCHITECTURAL PLANS. REVISE AS
 REQUIRED.
 ALSO, REVISE ORIENTATION OF WINDOWS. NOT ALL WINDOWS
 ARE LOCATED ON THE WEST SIDE. SEE PLANS AND REVISE AS
 REQUIRED.
 D) REVISE CEILING TYPE ITEM #10A. THERE IS NO ATTIC.
 THERE IS ANOTHER APARTMENT ON TOP OF THIS UNIT. REVISE
 AS REQUIRED.
 E) CLARIFY HOW GETTING R-4 INSULATION ON SLAB ON GRADE.
 REVISE AS REQUIRED. SEE PLANS.
 F) REVISE WALL TYPES ON ITEM #9. SEE PLANS AND REVISE
 AS REQUIRED. PLANS SHOW WOOD FRAMING CONSTRUCTION, NOT
 CONCRETE.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE SUBMITTED LATER AT TIME OF PERMIT
 PICK UP.
  
 3- ENGINEER NEEDS TO PROVIDE THE ENGINEERING FIRM
 MILTON ENGINEERING CONSULTANTS, P.A. CERTIFICATE OF
 AUTHORIZATION NUMBER ON ALL DRAWINGS AS REQUIRED BY
 SEC. 61G15--23.002(2) OF FLORIDA ADMINISTRATIVE CODE
 AND CHAPTER 471 FLORIDA STATUTE. (REPEAT COMMENT).
  
 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED DCA
 RULE 9B-72 FOR:
 A) ENTRY DOOR AS SHOWN ON PLANS. NONE SUBMITTED.
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 PAGE AND PAGE SHOWING THE CONNECTOR. NO NEED TO SUBMIT
 COMPLETE REPORT. THIS APPLIES TO CONNECTORS ONLY. OTHER
 PRODUCT APPROVALS NEED TO SUBMIT COMPLETE REPORT.
  
 5- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITING (NOT SIGNING AND SEALING) BY THE
 DESIGNER OF RECORD AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004. (REPEAT COMMENT).
  
 6- DESIGNER OF RECORD TO SPECIFY LEVEL OF ALTERATION
 FOR THIS PROJECT AS REQUIRED BY SEC. 301.5 OF 2004
 FLORIDA EXISTING BUILDING CODE. (REPEAT COMMENT).
  
 7- SCOPE OF WORK SPECIFIED ON PERMIT APPLICATION IS FOR
 REPLACEMENT OF INTERIOR DRYWALL, CABINETS AND OTHER
 INTERIOR FINISHES ONLY. ELECTRICAL AND PLUMBING
 FIXTURES WERE CROSSED OUT. PLANS SUBMITTED ARE FOR NEW
 WINDOWS AND WINDOW FRAMING AND FOR COMPLETE RENOVATION
 OF APARTMENT. CLARIFY SCOPE OF WORK ON PERMIT
 APPLICATION AND REVISE TOTAL VALUATION DECLARED TO
 REFLECT ALL WORK TO BE PERFORMED. SEC. 108.3 CITY
 AMENDMENTS TO FBC 2004.
  
 8- ARCHITECT NEEDS TO DATE PLANS WHEN THEY WERE SEALED
 AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE.
  
 9- ARCHITECT TO SPECIFY ON DRAWINGS IF FLOOR/CEILING
 ASSEMBLY IS GOING TO BE REPLACED. COMPLY WITH SEC. 503
 OF 2004 FLORIDA EXISTING BUILDING CODE.
 ***NOTE: UL SYSTEM L528 INCLUDES 16 FLOOR SYSTEMS.
 CLEARLY IDENTIFY WHICH FLOOR SYSTEM IS GOING TO BE
 INSTALLED. SEE L528 FOR DIFFERENT APPROVED SYSTEMS AND
 SELECT ONE.
  
 10- CONTRACTOR NEEDS TO UPDATE INSURANCE INFORMATION
 WITH PERMIT CLERK.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712