| Plan Review Notes For Permit 08060178 |
| Permit Number |
08060178 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-11-26 13:47:30 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- REVISE ENERGY CALCULATIONS: | | | A) GLASS SQUARE FOOTAGE ON ITEM 7A DOESN'T MATCH 7B. | | | REVISE AS REQUIRED. | | | B) ITEM 9: NEED TO INCLUDE COMMON WALLS AS REQUIRED BY | | | SEC. 13-602.1.ABC.1.1 FBC 2004. | | | C) ITEM 10: NEED TO INCLUDE COMMON CEILING/FLOORS AS | | | REQUIRED BY SEC. 13-604.1.ABC.1.2 FBC 2004. | | | D) REVISE CEILING AREA ON ITEM #10 TO MATCH CONDITIONED | | | AREA ON ITEM #6. COORDINATE WITH ITEM 1C ABOVE. | | | | | | 2- PROVIDE PRODUCT APPROVAL FOR OUTSWING ENTRY DOOR AS | | | SHOWN ON PLANS. PRODUCT APPROVAL SUBMITTED IS FOR | | | INSWING DOORS. | | | ***NOTE: ARCHITECT TO REVIEW AN APPROVE IN WRITING ALL | | | PRODUCT APPROVALS PRIOR TO SUBMITTAL TO THIS OFFICE. |
|