| 2008-06-26 17:53:37 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- REVISE LOCATION OF ATTIC ACCESS TO COMPLY WITH SEC. |
| | R807.1 OF 2004 FLORIDA RESIDENTIAL CODE. CHECK CLEAR |
| | ROOM ABOVE OPENING. |
| | |
| | 2- DESIGN INFORMATION ON SHEET 1 OF 2: |
| | A) ADD THE ATTIC LIVE LOAD AND SECOND FLOOR LIVE LOAD |
| | AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | B) SPECIFY BUILDING EXPOSURE USED FOR THE DESIGN AS |
| | REQUIRED BY SEC. R301.2.1.4 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE SUBMITTED AT TIME OF PRINTING THE |
| | PERMIT. |
| | |
| | 4- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| | (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE. BRING |
| | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| | DUE. |
| | |
| | 5- OWES $549.69 FOR RADON FEES AND UPDATED VALUATION AS |
| | REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 6- PROVIDE COMPLETE SECTION/DETAILS AND SPECIFICATIONS |
| | FOR STAIRWAY AND RAILINGS TO SHOW COMPLIANCE WITH TABLE |
| | R301.5, SEC. R311.5.1, SEC. R311.5.3 , SEC. R311.5.6.1 |
| | AND SEC. R312 OF 2004 FLORIDA RESIDENTIAL CODE. CLEARLY |
| | IDENTIFY NUMBER OF RISERS/TREADS AND PROVIDE ALL |
| | DIMENSIONS, INCLUDING STAIR DIMENSIONS. |
| | ***NOTE: CLARIFY CONSTRUCTION OF STAIRS AT BASE. |
| | DRAWINGS SUBMITTED DON'T SPECIFY ATTACHMENT AT BOTTOM |
| | OF STAIRS AND WHAT ARE STAIRS RESTING ON. DRAWINGS |
| | DON'T SHOW ANY INFORMATION. |
| | |
| | 7- CLEARLY IDENTIFY DISTANCE BETWEEN PROPOSED BUILDING |
| | AND ADJACENT BUILDINGS (EVEN ON ADJACENT LOTS) TO |
| | VERIFY COMPLIANCE WITH SEC. R302 OF 2004 FLORIDA |
| | RESIDENTIAL CODE REGARDING WALLS FIRE RATING AND |
| | PERCENTAGE OF OPENINGS. |
| | |
| | 8- SPECIFY FIREBLOCKING IN WALL SECTIONS AS REQUIRED BY |
| | SEC. R602.1.2 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 9- PROVIDE PRODUCT APPROVAL (2 COPIES ) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) ROOF SHINGLES. |
| | B) GARAGE OVERHEAD DOOR. SEE PLAN FOR SIZE. |
| | C) GARAGE SIDE DOOR. |
| | D) FRENCH DOORS ON SECOND FLOOR. |
| | E) PRECAST LINTELS. |
| | F) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. |
| | G) SINGLE HUNG WINDOWS. NOA 03-0910.03 WAS SUPERSEDED. |
| | SEE ATTACHED COPY FROM DADE COUNTY WEBSITE. NEED TO |
| | PROVIDE CURRENT NOA. |
| | |
| | 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 11- PROVIDE COMPLETE SPECIFICATIONS FOR GARAGE |
| | SEPARATION AS REQUIRED BY SEC. R309.2 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 12- PLEASE BRING REVISED PLANS FOR HISTORIC RE-STAMP |
| | PRIOR TO SUBMITTAL TO THIS OFFICE TO AVOID DELAYS. |
| | |