| 2009-06-15 14:37:50 | |
| | |
| | |
| | |
| | ** DENIED REVISIONS * |
| | |
| | 1) NOTE: E-3 SUBMITTED AS REVISED YET THERE ARE NO |
| | REVISIONS FROM THE RECORD SET OF PLANS. THE LAST |
| | REVISED SHEET NOTED IN THE TITLE BLOCK IS FROM |
| | 7/13/2008. THE NEW SHEET E-3 SUBMITTED HAS THE SAME |
| | REVISION DATED 7/13/2008. |
| | ** PLEASE ONLY SUBMIT SHEETS WHICH ARE INDEED BEING |
| | REVISED. |
| | |
| | 2) NOTE: PLEASE SEE E-1. NOTE ON THE SCOPE OF WORK HAS |
| | BEEN REVISED WITH THE REV #2, HOWEVER IT IS UNCLEAR |
| | WHAT THE REVISION IS? THE SENTENCE IN THIS NOTE STATES: |
| | * CONNECT NEW TANKS TO*. WHAT ARE THE NEW TANKS BEING |
| | CONNECTED TO? PLEASE COMPLETE NOTES FOR REVIEW AND |
| | COORDINATION FOR CODE COMPLIANCE. |
| | NEC 514 AND FBC 106.5, 106.1.1 FOR CLARITY AND |
| | COORDINATION OF PLANS. |
| | |
| | 3) NOTE: PLEASE COORDINATE PLANS. THE PLANS FOR E-2 NOW |
| | INDICATE THAT THE EXISTING PANEL G WHICH WAS BEING |
| | REPLACED IS NOW GOING TO REMAIN. HOWEVER THE RISER |
| | STILL INDICATES THE PANEL G AS A 20 CIRCUIT MLO YET THE |
| | REVISED PANEL HAS NOW GONE FROM THE QO 24 ON RECORD |
| | PLANS TO A QO16. |
| | WHICH ONE WILL IT BE? THE NEW REVISED PANEL SCHEDULE |
| | SHOWS 16, BUT THIS IS IN CONFLICT WITH THE RISER NOTES. |
| | |
| | 4) NOTE: PLEASE PROVIDE MORE INFORMATION ON STP RELAYS. |
| | THE RISER HAS NOW BEEN REVISED TO REMOVE ALL STP RELAYS |
| | HOWEVER THE PANEL SCHEDULE STILL LISTS FOUR. THE ONLY |
| | ONE REVISED WAS FOR *FUTURE DIESEL STP*. |
| | PLEASE COORDINATE. |
| | NEC 514, AND FBC 106.5, 106.1.1 FOR CLARITY AND |
| | COORDINATION OF RECORD PLANS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |