2008-06-19 09:42:26****************PROVISO****************
 A) FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE
 GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF
 GENERATOR PLACEMENT.
 NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET
 CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES
 SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS
 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR
 TO FINAL INSPECTION.
  
 B)PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 C)IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]