Plan Review Notes
Plan Review Notes For Permit 08060110
Permit Number 08060110
Review Stop G
Sequence Number 1
Notes
Date Text
2008-06-06 09:50:17GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 NOTE: THE SUBMITTED GAS PLANS ARE INDICATING A
 GENERATOR, HOWEVER THE MASTER PERMIT NUMBER REFERENCED
 ON THE PERMIT APPLICATION (07080952) DOES NOT HAVE AN
 APPROVED GENERTOR FOR THAT PERMIT. A SEPERATE
 RESIDENTIAL GENERATOR PERMIT APPLICATION IS REQUIRED
 FOR THE PROPOSED GENERATOR. ALL PERMIT APPLICATIONS
 MUST BE SUBMITTED TOGETHER TO EXPIDITE THE REVIEW
 PROCESS. PLEASE REFERENCE THE CITY OF WEST PALM BEACH
 RESIDENTIAL GENERATOR PLAN REVIEW REQUIRED INFORMATION
 ATTACHED TO THE GAS COMMENTS TO HELP IN THE GENERATOR
 PERMIT PROCESS.
  
 NOTE: GAS PLAN REVIEW PER "THE CITY OF WEST PALM BEACH
 GAS PERMIT APPLICATION REQUIREMENTS" AND THE FBC-2004
 W/07 REV. FUEL GAS CODE. PLEASE REFERENCE THE CITY OF
 WEST PALM BEACH GAS PERMIT APPLICATION REQUIREMENTS
 ATTACHED TO THE GAS COMMENTS TO ASSIST IN FUTURE
 PERMTS.
  
 1. THE SUBMITTED GAS ISOMETRIC DOES NOT INDICATE
 CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE. PER
 FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 2. THE SUBMITTED GAS ISOMETRIC DOES NOT CLEARLY
 INDICATE PIPING MATERIAL OR PIPE SIZES TO SOME OF THE
 ABOVE GROUND GAS PIPE. CLEARLY INDICATE PIPING MATERIAL
 AND SIZES TO ALL CUT SECTIONS OF PIPE. PER FBC-2004
 FUEL GAS SECTION 401.1 SCOPE.
  
 3. THE SUBMITTED GAS PERMIT AND THE PLANS ARE NOT
 INDICATING THE TYPE OF GAS BEING USED, (LP OR NATURAL).
 A GAS PLAN REVIEW CAN NOT BE DONE UNLESS THE TYPE OF
 GAS BEING USED IS CLEARLY INDICATED ON THE PLANS. PER
 FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 4. NOTE: PLANS ARE INDICATING SYSTEM AS 0.5 PSI,
 HOWEVER THE GAS TYPE IS NOT INDICATE. IF GAS IS NATURAL
 GAS PIPING IS NOT SIZED CORRECTLY PER FBC-2004 FUEL GAS
 TABLES 402.4(2) AND 402.4(20). REFERENCE THE RED LINE
 CORRECTIONS AND THE SIZING TABLES ATTACHED TO THE GAS
 COMMENTS INDICATING THIS.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 A} THE WATER HEATER DOES NOT INDICATE A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY (EXAMPLES ARE
 UL, CSA, OR AGA).
  
 B} THE STOVE HAS NO INDICATION OF BTU LOAD CAPACITY OR
 A LISTING LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY (EXAMPLES ARE UL,CSA OR AGA).
  
 6. A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING FOR
 THE GENERATOR LOCATION.
  
 7. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  