Plan Review Notes
Plan Review Notes For Permit 08060102
Permit Number 08060102
Review Stop E
Sequence Number 6
Notes
Date Text
2008-12-26 14:15:10** DENIED 6TH REVIEW **
  
 1) NOTE: PLANS AND RISER STILL NEED SOME COORDINATION.
 PLANS SHOW EXISTING PANEL *C* TO REMAIN HOWEVER THE
 RISER AND DPA DOES NOT INDICATE ANY FEED TO ANY PANEL
 *C*. WHERE IS THIS PANEL FED FROM?
 WHAT IS THE LOAD ON THIS PANEL?
 DPA SCHEDULE LIST SEVERAL PANELS AND EQUIPMENT HOWEVER
 NOT THIS PANEL.
 240.4,310.16,220,230,215.5 ETC.
 ON PREVIOUS REVIEW THE ELECTRICAL RISER WHICH HAD
 PROPOSED NEW DISCONNECT FOR A/C EQUIPMENT ONLY HAS NOT
 BEEN REMOVED. THE DISCONNECT STILL SHOWN AS EXISTING
 HAS NEVER BEEN PERMITTED. THE KEY NOTES ON SHEET E3.1
 STILL REFERS TO THIS EQUIPMENT AS NEW TO BE INSTALLED.
  
 2) NOTE: PLEASE REVISE THE APPLIED VALUE FOR THE NEW
 COMPLETE SCOPE OF WORK. THE NEW ROOM, MAIN ELECTRICAL
 DISTRIBUTION SYSTEM WAS NOT PART OF THE ORIGINAL SCOPE
 OF WORK WHICH WAS APPLIED FOR UNDER A MECHANICAL
 PRIMARY PERMIT.
 FBC 108.3
 THE PREVIOUS APPLICATION VALUES WERE BASED ON OLD SCOPE
 OF WORK WHICH HAS SUBSTANTIALLY INCREASED.
  
 3) NOTE: PLANS INDICATE NEW FACP. HOW IS THIS FED, FROM
 WHERE AND CIRCUIT?
 PLEASE SEE POSSIBLE FIRE MARSHAL REVIEW COMMENTS.
  
  
 *** NO FEE PER FS 553.80(2)(B) IS ASSESSED AS PLANS
 HAVE CHANGED OR BEEN REVISED IN ONE WAY AS TO NOT HAVE
 THE SAME SPECIFIC CODE DEFICIENCY THREE OR MORE TIMES.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  