| 2008-12-26 14:15:10 | ** DENIED 6TH REVIEW ** |
| | |
| | 1) NOTE: PLANS AND RISER STILL NEED SOME COORDINATION. |
| | PLANS SHOW EXISTING PANEL *C* TO REMAIN HOWEVER THE |
| | RISER AND DPA DOES NOT INDICATE ANY FEED TO ANY PANEL |
| | *C*. WHERE IS THIS PANEL FED FROM? |
| | WHAT IS THE LOAD ON THIS PANEL? |
| | DPA SCHEDULE LIST SEVERAL PANELS AND EQUIPMENT HOWEVER |
| | NOT THIS PANEL. |
| | 240.4,310.16,220,230,215.5 ETC. |
| | ON PREVIOUS REVIEW THE ELECTRICAL RISER WHICH HAD |
| | PROPOSED NEW DISCONNECT FOR A/C EQUIPMENT ONLY HAS NOT |
| | BEEN REMOVED. THE DISCONNECT STILL SHOWN AS EXISTING |
| | HAS NEVER BEEN PERMITTED. THE KEY NOTES ON SHEET E3.1 |
| | STILL REFERS TO THIS EQUIPMENT AS NEW TO BE INSTALLED. |
| | |
| | 2) NOTE: PLEASE REVISE THE APPLIED VALUE FOR THE NEW |
| | COMPLETE SCOPE OF WORK. THE NEW ROOM, MAIN ELECTRICAL |
| | DISTRIBUTION SYSTEM WAS NOT PART OF THE ORIGINAL SCOPE |
| | OF WORK WHICH WAS APPLIED FOR UNDER A MECHANICAL |
| | PRIMARY PERMIT. |
| | FBC 108.3 |
| | THE PREVIOUS APPLICATION VALUES WERE BASED ON OLD SCOPE |
| | OF WORK WHICH HAS SUBSTANTIALLY INCREASED. |
| | |
| | 3) NOTE: PLANS INDICATE NEW FACP. HOW IS THIS FED, FROM |
| | WHERE AND CIRCUIT? |
| | PLEASE SEE POSSIBLE FIRE MARSHAL REVIEW COMMENTS. |
| | |
| | |
| | *** NO FEE PER FS 553.80(2)(B) IS ASSESSED AS PLANS |
| | HAVE CHANGED OR BEEN REVISED IN ONE WAY AS TO NOT HAVE |
| | THE SAME SPECIFIC CODE DEFICIENCY THREE OR MORE TIMES. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |