Plan Review Notes
Plan Review Notes For Permit 08060102
Permit Number 08060102
Review Stop E
Sequence Number 5
Notes
Date Text
2008-11-17 08:48:27 
  
  
 ** FAILED **
  
 1) NOTE: PLEASE SEE NOTES FROM THE PREVIOUS REVIEW. AS
 THE SCOPE OF WORKED HAS CHANGED FROM THE ORIGINAL
 REVIEW TO INCLUDE A NEW ELECTRICAL SERVICE, NEW
 ELECTRICAL ROOM ETC. AS STATED ON PREVIOUS REVIEW AS
 THE PRIMARY SCOPE OF WORK IS NO LONGER MECHANICAL THE
 MECHANICAL CONTRACTOR MAY NOT APPLY FOR THE MAIN SCOPE
 OF WORK. THE RESPONSE FROM THE DESIGNER MENTIONS THE
 MECHANICAL CONTRACTOR WILL APPLY. PLEASE SEE THE
 PREVIOUS REVIEW WHICH STATED TO SUBMIT COMPLETED PLANS
 FOR THE NEW ROOMS BEING CONSTRUCTED AND REMODELED.
 PLEASE ALSO BE SURE TO SUBMIT ANY PRODUCT APPROVALS FOR
 EXTERIOR.
 FBC 106.1.1, 105.1
  
  
 2) NOTE: THE DESIGN WATTAGE IS BEING SHOWN OVER THE
 ALLOWED WATTAGE AS SHOWN ON SHEET E2.1. PLEASE SEE
 13-415.2, 13-415.2.ABC.1.1, .1.2, TABLE 13-415.2.B.
 MAY NOT EXCEED SPECIFIC ALLOWANCES.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  