Text |
| 2008-11-17 08:48:27 | |
| | |
| | |
| | ** FAILED ** |
| | |
| | 1) NOTE: PLEASE SEE NOTES FROM THE PREVIOUS REVIEW. AS |
| | THE SCOPE OF WORKED HAS CHANGED FROM THE ORIGINAL |
| | REVIEW TO INCLUDE A NEW ELECTRICAL SERVICE, NEW |
| | ELECTRICAL ROOM ETC. AS STATED ON PREVIOUS REVIEW AS |
| | THE PRIMARY SCOPE OF WORK IS NO LONGER MECHANICAL THE |
| | MECHANICAL CONTRACTOR MAY NOT APPLY FOR THE MAIN SCOPE |
| | OF WORK. THE RESPONSE FROM THE DESIGNER MENTIONS THE |
| | MECHANICAL CONTRACTOR WILL APPLY. PLEASE SEE THE |
| | PREVIOUS REVIEW WHICH STATED TO SUBMIT COMPLETED PLANS |
| | FOR THE NEW ROOMS BEING CONSTRUCTED AND REMODELED. |
| | PLEASE ALSO BE SURE TO SUBMIT ANY PRODUCT APPROVALS FOR |
| | EXTERIOR. |
| | FBC 106.1.1, 105.1 |
| | |
| | |
| | 2) NOTE: THE DESIGN WATTAGE IS BEING SHOWN OVER THE |
| | ALLOWED WATTAGE AS SHOWN ON SHEET E2.1. PLEASE SEE |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2, TABLE 13-415.2.B. |
| | MAY NOT EXCEED SPECIFIC ALLOWANCES. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |