| 2008-10-03 08:27:32 | |
| | ** DENIED 4TH REVIEW ** |
| | |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE PLANS HAVE NOW BEEN REVISED TO |
| | INDICATE A COMPLETE NEW ELECTRICAL RISER CALLING THE |
| | DISCONNECT FOR AC EQUIPMENT AS EXISTING. HOW IS THIS |
| | POSSIBLE WHEN THIS PERMIT APPLICATION WAS TO INSTALL |
| | THIS SAME DISCONNECT WHICH IS NOW SHOWN AS EXISTING? |
| | IF THE SCOPE OF WORK IS NOW TO INCLUDE A NEW MDP, |
| | ELECTRICAL ROOMS, AND OTHER ROOMS AS SHOWN ON |
| | ELECTRICAL PLANS, THEN PLEASE REVISE THE ENTIRE SET OF |
| | PLANS. PLEASE REVISE PERMIT APPLICATION, PERMIT |
| | VALUATION ETC. THE APPLICATION AS SUBMITTED IS BY THE |
| | MECHANICAL CONTRACTOR THE SPECIFIED WORK OF: * THE |
| | ADDITION OF ONE ROOF MOUNTED OUTSIDE AIR PACKAGE UNIT*. |
| | THESE PLANS SUGGEST BUILDING A NEW SERVICE ETC IN A |
| | ROOM WHICH DOES NOT EXIST AT THIS TIME. THIS IS BASED |
| | ON PLANS WHICH WERE PREVIOUSLY SUBMITTED WHICH DID NOT |
| | CONTAIN THIS ROOM AND IT WAS BEING CREATED FOR NEW |
| | SERVICE. |
| | COORDINATION WITH ALL PARTIES INVOLVED NEEDS TO BE |
| | ACHIEVED BEFORE RE-SUBMITTING PLANS FOR REVIEW. A SITE |
| | VISIT MAY BE REQUESTED TO SEE WHAT EXISTS AND WHAT IS |
| | ACTUALLY ON-SITE. PLEASE CONTACT THIS OFFICE SO THIS |
| | MAY BE ARRANGED. NO FURTHER REVIEWS WILL BE DONE UNTIL |
| | EQUIPMENT AND CONDITIONS IN THE FIELD CAN BE CONFIRMED. |
| | |
| | 2) NOTE: RISER SHOWS WHAT ONE WOULD ASSUME AS THE MDP |
| | AS DPA. PLEASE ADJUST THIS MISPRINT. |
| | 408.4 |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| | |
| | 3) NOTE: THE RISER NOW CALLS FOR A NEW PANEL *EM*. |
| | TYPICALLY EM DESIGNATION IS FOR EMERGENCY PANELS YET NO |
| | OTHER BACK UP SYSTEMS ARE SHOWN. IS THIS AN EMERGENCY |
| | PANEL OR JUST USING THIS DESIGNATION? |
| | 700,701, 702 ETC |
| | FBC 106.1.1, FOR ADDITIONAL INFORMATION AND CLARITY OF |
| | PLANS. |
| | |
| | 4) NOTE: IF THE WORK FOR ROOMS, LIGHTING ETC BECOMES |
| | PART OF THE SCOPE OF WORK PLEASE PROVIDE LIGHTING |
| | PERFORMANCE CALCULATIONS PER 13-415.2, |
| | 13-415.2.ABC.1.1, .1.2. |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |