Plan Review Notes
Plan Review Notes For Permit 08060102
Permit Number 08060102
Review Stop E
Sequence Number 4
Notes
Date Text
2008-10-03 08:27:32 
 ** DENIED 4TH REVIEW **
  
  
  
  
 1) NOTE: PLEASE SEE THE PLANS HAVE NOW BEEN REVISED TO
 INDICATE A COMPLETE NEW ELECTRICAL RISER CALLING THE
 DISCONNECT FOR AC EQUIPMENT AS EXISTING. HOW IS THIS
 POSSIBLE WHEN THIS PERMIT APPLICATION WAS TO INSTALL
 THIS SAME DISCONNECT WHICH IS NOW SHOWN AS EXISTING?
 IF THE SCOPE OF WORK IS NOW TO INCLUDE A NEW MDP,
 ELECTRICAL ROOMS, AND OTHER ROOMS AS SHOWN ON
 ELECTRICAL PLANS, THEN PLEASE REVISE THE ENTIRE SET OF
 PLANS. PLEASE REVISE PERMIT APPLICATION, PERMIT
 VALUATION ETC. THE APPLICATION AS SUBMITTED IS BY THE
 MECHANICAL CONTRACTOR THE SPECIFIED WORK OF: * THE
 ADDITION OF ONE ROOF MOUNTED OUTSIDE AIR PACKAGE UNIT*.
 THESE PLANS SUGGEST BUILDING A NEW SERVICE ETC IN A
 ROOM WHICH DOES NOT EXIST AT THIS TIME. THIS IS BASED
 ON PLANS WHICH WERE PREVIOUSLY SUBMITTED WHICH DID NOT
 CONTAIN THIS ROOM AND IT WAS BEING CREATED FOR NEW
 SERVICE.
 COORDINATION WITH ALL PARTIES INVOLVED NEEDS TO BE
 ACHIEVED BEFORE RE-SUBMITTING PLANS FOR REVIEW. A SITE
 VISIT MAY BE REQUESTED TO SEE WHAT EXISTS AND WHAT IS
 ACTUALLY ON-SITE. PLEASE CONTACT THIS OFFICE SO THIS
 MAY BE ARRANGED. NO FURTHER REVIEWS WILL BE DONE UNTIL
 EQUIPMENT AND CONDITIONS IN THE FIELD CAN BE CONFIRMED.
  
 2) NOTE: RISER SHOWS WHAT ONE WOULD ASSUME AS THE MDP
 AS DPA. PLEASE ADJUST THIS MISPRINT.
 408.4
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 3) NOTE: THE RISER NOW CALLS FOR A NEW PANEL *EM*.
 TYPICALLY EM DESIGNATION IS FOR EMERGENCY PANELS YET NO
 OTHER BACK UP SYSTEMS ARE SHOWN. IS THIS AN EMERGENCY
 PANEL OR JUST USING THIS DESIGNATION?
 700,701, 702 ETC
 FBC 106.1.1, FOR ADDITIONAL INFORMATION AND CLARITY OF
 PLANS.
  
 4) NOTE: IF THE WORK FOR ROOMS, LIGHTING ETC BECOMES
 PART OF THE SCOPE OF WORK PLEASE PROVIDE LIGHTING
 PERFORMANCE CALCULATIONS PER 13-415.2,
 13-415.2.ABC.1.1, .1.2.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  