| 2008-09-11 10:12:10 | ** DENIED REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: AS NOTED ON PREVIOUS REVIEW AND ON MEETINGS |
| | HELD VIA PHONE. ALL PROPOSED SERVICE(S) FOR BUILDING |
| | NEED TO BE SHOWN IN ORDER TO SEE *IF* AN ADDITIONAL |
| | SERVICE CAN BE GRANTED FOR THE MECHANICAL EQUIPMENT |
| | ALONE. THERE IS NO INFORMATION SHOWN. THE PHONE MEETING |
| | CONSISTED INFORMING THIS OFFICE ANOTHER NEW SERVICE FOR |
| | THIS BUILDING IS PLANNED AND ON DRAWINGS HOWEVER HAVE |
| | NOT BEEN SUBMITTED AS OF YET. |
| | 230.2 |
| | |
| | ** PLEASE COMPLETE PLANS WITH ALL ELECTRICAL. FBC |
| | 106.3.5.1.2, 106.1.1, 2005 NEC |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |