Plan Review Notes
Plan Review Notes For Permit 08060102
Permit Number 08060102
Review Stop E
Sequence Number 2
Notes
Date Text
2008-07-30 09:51:43 
 ** DENIEDREVIEW **
  
  
 1) NOTE:SERVICE AS SHOWN NOT PERMITTED PER 230.2. NO
 OTHER MAIN ARE SHOWN. THE PLANS ARE NOT COMPLETE
 SHOWING ALL ASPECTS OF THE ELECTRICAL SERVICE,
 LOCATIONS, SIZES, MAINS, GROUPING ETC
 110.9,230.2,230.70,230.71,230.72,230.76,230.79 ETC
 PLANS DO NOT SHOW COMPLETE SEPARATION FROM OTHER NEW
 STRUCTURE. THE NEW STRUCTURE CURRENTLY BEING BUILT WAS
 GOING TO FEED THIS BUILDING WITH ANOTHER SERVICE FROM
 ANOTHER FPL TRANSFORMER.
 PLEASE SEE THE FBC FOR DEFINITIONS OF A BUILDING AND
 REQUIRED SEPARATIONS. A FOUR RATED WALL IS NOT THE ONLY
 REQUIREMENT.
 THE PLANS ARE NOT COMPLETE WITH MUCH INFORMATION NEEDED
 TO BE SHOWN. A CALL WAS PLACED TO THE ENGINEERS OFFICE
 ON TWO OCCASIONS.
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  