2009-01-21 11:34:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. PLEASE PROVIDE UPDATED VALUE. SCOPE OF WORK HAS
 INCREASED (NOTE NEW PLANS DATED 12/2/08, NOT A PART OF
 FIRST REVIEW).
  
 2. PLEASE SPECIFY HEAD OF WALL DETAIL FOR THE NEW RATED
 WALL, FBC706.4, FBC 708.4.
  
 3. PROVIDE A DETAIL FOR UL465 ON THE PLAN.
  
 4. INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6, BUILDING
 HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, OCCUPANCY
 CLASSIFICATION FBC 3.
  
 5. PROVIDE DIMENSION BETWEEN THE PROPOSED NEW ELECTRIC
 ROOM SOUTH WALL AND THE EXISTING DRESSING ROOM DOOR
 (BETWEEN DRESSING ROOM AND CORRIDOR) TO SHOW
 MANEUVERING CLEARANCE REQUIRED, FBC FIGURE 11 25.
  
 6. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC*106.3.3.
  
 7. DECLARE WIND DESIGN CRITERIA, FBC1603.1.4.
  
 8. THE PROPOSED ELECTRIC ROOM APPEARS TO EXIT DIRECTLY
 TO THE OUTSIDE, BUT DOUBLE LINES ARE SHOWN ON THE PLAN
 GOING TO THE PROPERTY LINE OUSTIDE THE DOOR. PLEASE
 PROVIDE A DESIGNATION FOR THIS AREA; IS IT INSIDE OR
 OUTSIDE? NOT ENOUGH INFORMATION PROVIDED TO DETERMINE
 USE OF THIS .
  