| 2009-10-30 08:18:35 | ** TEMP FAILED. ** |
| | |
| | 1) NOTE: PLANS WERE PLACED INTO TEMPORARY FAILED STATUS |
| | ON OCTOBER 8H, 2009. RISER WAS REVISED REMOVING |
| | GROUNDING ELECTRODE BOND BETWEEN BOTH SERVICES. THE |
| | LETTER ATTACHED MENTIONS THE CITY OF WEST PALM BEACH |
| | CONSIDERS BOTH THE NEW ADDITION AND EXISTING BUILDINGS |
| | AS TWO SEPARATE BUILDINGS THEREFORE REMOVING THE |
| | GROUNDING ELECTRODE BONDING BOTH SERVICES. |
| | THE PREVIOUS CONVERSATIONS WERE THAT IT WAS THE DESIRE |
| | OF THE DESIGN TEAM TO HAVE TWO SEPARATE BUILDINGS |
| | ALLOWING TWO SEPARATE SERVICES. IN THOSE DISCUSSIONS |
| | AND PREVIOUS PLAN REVIEWS IT WAS GONE OVER THAT NO |
| | SYSTEMS OR METALLIC PATHS FROM EACH BUILDING COULD PASS |
| | THROUGH OR BE INTERCONNECTED FROM EACH BUILDING OTHER |
| | WISE SERVICES WOULD BE REQUIRED TO BE BONDED. |
| | THE RISER DIAGRAM HAS NOW BEEN REVISED TO REMOVE THE |
| | GROUNDING ELECTRODE BOND. |
| | THIS REVIEWER PLACED A CALL TO JOHN CHIRGWIN FROM KAMM |
| | CONSULTING TO GO OVER ANY POSSIBLE METALLIC PATHS. MR. |
| | CHIRGWIN DID NOT HAVE THE INFORMATION AND WAS GOING TO |
| | GET BACK TO THIS OFFICE. |
| | TO DATE OF THIS REVIEW ENTRY THIS HAS NO OCCURRED. |
| | |
| | |
| | THERE CAN BE NO METALLIC PATHS BETWEEN BUILDINGS. THE |
| | SEPARATION INFORMATION PROVIDED ON ARCHITECTURAL PLANS |
| | INDICATES A 4HR FIRE WALL FOR SEPARATION. PER THE |
| | DEFINITIONS IN THE FLORIDA BUILDING CODE THESE CAN BE |
| | CONSIDERED TWO SEPARATE BUILDINGS. SEPARATE BUILDINGS |
| | INCLUDE ALL SYSTEMS. |
| | THIS WAS GONE OVER ON NUMEROUS OCCASIONS BEFORE THIS |
| | REVIEW. IF A METALLIC PATH EXISTS, THEN SERVICES SHALL |
| | BE BONDED. SIZING PER 250.66 |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |