| Plan Review Notes For Permit 08060102 |
| Permit Number |
08060102 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-01-27 09:08:18 | APPROVED PROVISO | | | | | | 1. THE NEW ELECTRICAL CLOSET OR ROOM SHALL BE PROPERLY | | | PROTECTED WITH FIRE SPRINKLERS IF THE REMAINDER OF THE | | | BUILDING IS PROTECTED. | | | | | | 2. THE NEW LAY IN ACCOUSTICAL CEILING IS TO COMPLY WITH | | | APPLICABLE FLAME SPREAD REQUIREMENTS. | | | | | | 3. THE NEW FIRE ALARM CONTROL PANEL IS TO BE TESTED | | | AFTER INSTALLATION. APPROPRIATE PLANS AND PERMITS WILL | | | BE REQUIRED. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|