Plan Review Notes
Plan Review Notes For Permit 08060102
Permit Number 08060102
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-30 15:57:58 
  
  
 DENIED
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE DISCONNECT IS SHOWN AS A SEPARATE SERVICE (MAIN
 1 OF 1, SHEET EO.1 AND E3.1) AND IN VIOLATION OF
 ARTICLE 230.2, 2005 NEC.THE DISCONNECT FOR THE NEW
 MECHANICAL UNIT MUST BE FEED FROM THE EXISTING
 SERVICE.
  
  
 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO
 BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5
 NEC 2005.
  
 3} 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT OUTLET
 A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET
 SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING MEANS.**THE RECEPTACLE MOUNTING
 TO THE UNIT ON SHEET E3.1APPEARS AS THOUGH THE CONDUIT
 IS GOING INTO THE UNIT AND NOTE #3 INDICATES EXISTING
 POWER, PLEASE CLARIFY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718