| 2008-06-30 15:57:58 | |
| | |
| | |
| | DENIED |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THE DISCONNECT IS SHOWN AS A SEPARATE SERVICE (MAIN |
| | 1 OF 1, SHEET EO.1 AND E3.1) AND IN VIOLATION OF |
| | ARTICLE 230.2, 2005 NEC.THE DISCONNECT FOR THE NEW |
| | MECHANICAL UNIT MUST BE FEED FROM THE EXISTING |
| | SERVICE. |
| | |
| | |
| | 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL |
| | SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO |
| | BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5 |
| | NEC 2005. |
| | |
| | 3} 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION |
| | EQUIPMENT OUTLET |
| | A 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND |
| | WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING, |
| | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET |
| | SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE |
| | EQUIPMENT DISCONNECTING MEANS.**THE RECEPTACLE MOUNTING |
| | TO THE UNIT ON SHEET E3.1APPEARS AS THOUGH THE CONDUIT |
| | IS GOING INTO THE UNIT AND NOTE #3 INDICATES EXISTING |
| | POWER, PLEASE CLARIFY. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |