| Plan Review Notes For Permit 08060091 |
| Permit Number |
08060091 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-06-16 11:02:07 | *****UNSAT***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER | | | ACCESS TO / EGRESS FROM THE OTHER UNITS ON THE SAID | | | FLOOR OR THE BUILDING. | | | | | | 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 5.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW | | | WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 6.SHOW AND/OR EXPLAIN HOW THE FIRE SPRINKLER HEADS | | | AND SMOKE ALARMS WITHIN THE DWELLING UNIT WILL BE | | | IMPACTED AS A RESULT OF THE REMODEL. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|