| 2008-06-12 15:45:22 | BUILDING PLAN REVIEW |
| | PERMIT: 08060091 |
| | ADD: 1701 S. FLAGLER DR. #1802 |
| | CONT: PROJECT ONE INTERIORS INC. |
| | TEL: (561)541-4555 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODES. FLAGLER DR. |
| | #1802 |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THIS CODE. |
| | |
| | 4)PROVIDE A WALL DETAIL FOR THE NEW WALLS. THE DETAIL |
| | SHALL INCLUDE THE STUD SPACING, THE TYPE OF STUDS METAL |
| | OR WOOD AND THE TYPE OF DRYWALL OR SURFACE FINISH. |
| | ADDITIONAL INFORMATION REQUIRED 106.1.2* |
| | |
| | 5)DUE TO THE FACT THAT THIS IS A HIGH-RISE BUILDING |
| | THE DESIGN PRESSURES FOR THE SLIDING GLASS DOOR SHALL |
| | BE DESIGN PER ASCE 7 AND CALCULATED BY A REGISTERED |
| | PROFESSIONAL FBC 1609.1.1. THE PRODUCT APPROVAL SHALL |
| | INDICATE BY CIRCLING OR HI-LIGHT THE TYPE OF GLASS AND |
| | THE DESIGN PRESSURES FOR THE NEW DOOR FROM THE TABLES |
| | PROVIDED IN THE INSTALLATION REPORT. PLEASE CHECK THE |
| | PRODUCT APPROVAL AND MAKE SURE THE DOOR CAN BE USED AT |
| | THIS LOCATION. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION AND NATURE |
| | AND EXTENT OF THE WORK PROPOSED 106.1.1 |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |