| 2008-06-10 16:48:50 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | |
| | SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY |
| | |
| | _XX_1.DESIGN PRESSURES FOR BUILDINGS OVER 60FEET |
| | ARE REQUIRED TO BE DESIGNED USING ASCE7, FBC1609.1.1 |
| | AND MUST BE DONE BY A DESIGN PROFESSIONAL. DOCUMENTS |
| | PREPARED BY AN ARCHITECT OR ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED SEALED ORIGINALS |
| | FAC61G15, FAC61G1 16. |
| | THE ENGINEERING SPECIFIES -95.09, -84.11, BUT THE |
| | INSTALLATION SCHEDULE SPECIFIES -71.9 AND -76.1. |
| | PLEASE REVISE. |
| | |
| | _XX_2.TWO SETS OF PERMIT DOCUMENTS REQUIRED. |
| | |
| | ____3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE |
| | OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| | ANOTHER FORMAT, FBC*106.TWO SETS REQUIRED. |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | ____4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG. |
| | |
| | ____5.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC |
| | R310. |
| | |
| | ____6.PROVIDE A FLOOR PLAN SHOWING WHERE THE |
| | SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH |
| | CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3 |
| | ABOVE. |
| | |
| | ____8.REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE |
| | FOR EXPOSURE B.NOTE THAT THE DEFINITION FOR EXPOSURE |
| | C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC |
| | R301.2.1.4. |