2008-12-10 11:48:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE SEE THE PRODUCT APPROVAL, PAGE 11. A DESIGN
 PRESSURE OF -136 REQUIRES USE OF THE 120PSF COLUMN. THE
 CONNECTION TYPES 5 AND 7 ARE NOT PERMITTED FOR HIS
 DESIGN PRESSURE.
  
 PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  