| Plan Review Notes For Permit 08060067 |
| Permit Number |
08060067 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-06-10 15:38:52 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | | | | FROM PREVIOUS LIST: | | | | | | 1. DESIGN PRESSURES FOR BUILDINGS OVER 60FEET ARE | | | REQUIRED TO BE DESIGNED USING ASCE7, FBC1609.1.1 AND | | | MUST BE DONE BY A DESIGN PROFESSIONAL. DOCUMENTS | | | PREPARED BY AN ARCHITECT OR ENGINEER AND SUBMITTED FOR | | | PUBLIC RECORD ARE TO BE SIGNED SEALED ORIGINALS | | | FAC61G15, FAC61G1 16. | | | | | | ENGINEERING IS REQUIRED AS DISCUSSED.PLEASE NOTE THAT | | | YOUR COMPUTERIZED ENGINEERING (WHICH IS NOT THE SAME AS | | | CERTIFICATION BY A PE) WAS GENERATED FOR A BUILDING | | | HEIGHT OF 60, BUT THIS BUILDING IS 200FEET TALL.THE | | | UNIT'S LOCATION AFFECTS POSITIVE PRESSURE BUT NOT THE | | | NEGATIVE PRESSURES.I BELIEVE THAT I HAD A TELEPHONE | | | CONVERSATION WITH YOU AND STATED THAT IF YOU USED A | | | VERY CONSERVATIVE DESIGN PRESSURE, SUCH AS -100PSF, | | | THEN NO ENGINEERING WOULD BE REQUIRED.YOU HAVE | | | DESIGNED TO -60PSF; THIS IS NOT WHAT I WOULD CONSIDER | | | "VERY CONSERVATIVE"; THEREFORE, ENGINEERING IS | | | REQUIRED. | | | | | | 2.PROVIDE A COPY OF THE CONDO ASSOCIATION APPROVAL. | | | | | | |
|