Plan Review Notes
Plan Review Notes For Permit 08060046
Permit Number 08060046
Review Stop P
Sequence Number 3
Notes
Date Text
2008-09-09 15:25:53****************PROVISO****************
 SHEET M-1 NEEDS TO BE REVISED BEFORE FINAL TO REFLECT
 THE FOLLOWING:
  
 A} CHANGE TRAPZILLA MODEL TZ-325 TO TRAPZILLA MODEL
 TZ-400. PER RODNEY COMPO (ENVIRONMENTAL COMPLIANCE) AND
 FBC-2004 PLUMBING SECTION 701.1 SCOPE.
  
 B} CLEARLY INDICATE THAT FIXTURES P-6 (TRIPLE SINK) AND
 P-8 (BAR SINK) SHALL DISCHARGE THROUGH AN INDIRECT
 WASTE PIPE BY MEANS OF AN AIR GAP. PER FBC-2004
 PLUMBING SECTION 802.1.1 FOOD HANDLING.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]