| 2008-08-12 11:59:15 | PLUMBING PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WLLAS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW |
| | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW |
| | COMMENTS. |
| | |
| | 1. SHEET A-1 AND M-1 CLEARLY IDENTIFY ALL PLUMBING |
| | FIXTURES EXISTING AND PROPOSED WITH A FIXTURE |
| | SCHEDULE. |
| | NOTE: SOME FIXTURES THAT ARE BEING INDICATED ON SHEET |
| | M-1 EXISTING WATER AND SANITARY ISOMETRICS ARE NOT |
| | CLEARLY INDENTIFIED ON SHEET A-1 (P3, THREE HAND SINKS, |
| | WASHER). IF THESE FIXTURES ARE NOT ON THE NEW FLOOR |
| | PLAN THEY SHOULD BE DELETED TO AVOID FUTHER CONFUSION. |
| | PER FBC- PLUMBING SCTION 401.1 SCOPE, 601.1 SCOPE AND |
| | 701.1 SCOPE. |
| | |
| | **RESPONSE NOTED, HOWEVER ON RESUBMITTED PLAN SHEET |
| | M-1 WATER ISOMETRIC THERE ARE STILL TWO FIXTURES THAT |
| | ARE NOT CLEARLY IDENTIFIED. THERE IS ALSO A BAR SINK |
| | BEING IDENTIFIED ON THE WATER ISOMETRIC, HOWEVER THIS |
| | SINK IS NOT ON THE PLUMBING FIXTURE SCHEDULE. PLEASE |
| | KNOW THAT THIS FIXTURE IS BEING IDENTIFIED ON THE |
| | SANITARY ISOMETRIC AND THE FIXTURE SCHEDULE AS A P-8 |
| | HAND SINK. PLEASE KNOW THAT NOW THE MOP SINK IS BEING |
| | CLEARLY IDENTIFIED THAT IT NEEDS TO DRAIN INTO THE |
| | GREASE SYSTEM AND THE FLOW RATE TO THE GREASE TRAP SO |
| | NOTED ON THE FIXTURE SCHEDULE. PLEASE CORRECT AND |
| | CORRELATE THESE ITEMS PER FBC-2004 PLUMBING SECTIONS |
| | 401.1 SCOPE, 601.1 SCOPE AND 701.1 SCOPE. |
| | |
| | 2. "OK" COMMENT ADDRESSED. |
| | |
| | 3. SHEETS A-1 AND M-1 ARE INDICATING AN EXISTING |
| | GREASE INTERCEPTOR IN SIDE OF THE RESTAURANT, HOWEVER |
| | THERE IS NO SIZE BEING INDICATED FOR THE INTERCEPTOR. |
| | CLEARLY INDICATE THE SIZE OF THE INTERCEPTOR. PER FBC- |
| | PLUMBING SECTION 701.1 SCOPE AND PLEASE PROVIDE THE |
| | FOLLOWING |
| | PER MUNICIPAL CODE ARTICLE III SECTION 90-124, THE |
| | EXISTING/PROPOSED GREASE INTERCEPTOR SHALL BE SIZED AND |
| | LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE |
| | UTILITY DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE: |
| | (561) 822-2272, E-MAIL: [email protected] THE FAX NUMBER |
| | IS (561) 822-2287. NOTE: WRITTEN APPROVAL IS REQUIRED |
| | OF THE EXISTING/PROPOSED GREASE INTERCEPTOR FROM |
| | ENVIRONMENTAL COMPLIANCE BEFORE A PERMIT CAN BE |
| | ISSUED. |
| | |
| | **RESPONSE NOTED, HOWEVER PER E-MAIL BY RODNEY COMPO |
| | DATED 6/24/08 IT STATES THAT HE INSPECTED THE THE SITE |
| | AND THAT IT HAS AN OLD IN FLOOR GREASE TRAP. TRAP NEEDS |
| | TO BE UPDATED AND MOVED TO THE OUTSIDE, NEXT TO THE CAN |
| | WASH NEXT TO OR UNDER THE STAIRWAY. HE DOES SUGGEST |
| | THAT A TRAPZILLA SUPERCAPACITY GREASE TRAP WOULD WORK |
| | IN THIS LOCATION. PLEASE KNOW THAT PER MUNICIPAL CODE |
| | SECTION 90-124(7)(B) GREASE INTERCEPTORS (GREASE TRAPS) |
| | ARE TO BE INSTALLED OUTSIDE OF THE FOOD PREPERATION |
| | AREA. PLEASE KNOW THAT PER RODNEY COMPO'S ON SITE |
| | INSPECTION REVIEW AND THE MUNICIPAL CODE THE NEW |
| | TRAPZILLA SHALL BE LOCATED OUTSIDE. |
| | |
| | **THE FOLLOWING ARE NEW COMMENTS** |
| | |
| | 4. SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR |
| | (4) TIMES THE FEE. |
| | |
| | 5. SHEET M-1 WATER ISOMETRIC: CLEARLY INDICATE ON THE |
| | PLANS THAT THE DEVICES INDICATED FOR WATER HAMMER |
| | PROTECTION FOR THE FIXTURES ARE WATER-HAMMER ARRESTORS |
| | AND THAT THEY ARE NOT AIR CHAMBERS. PLEASE KNOW THAT |
| | AIR CHAMBERS ARE NOT APPROVED BY THE FBC-2004 PLUMBING |
| | SECTION 604.9 WATER HAMMER. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |