| 2008-06-16 15:18:10 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A-1 AND M-1 CLEARLY IDENTIFY ALL PLUMBING |
| | FIXTURES EXISTING AND PROPOSED WITH A FIXTURE |
| | SCHEDULE. |
| | NOTE: SOME FIXTURES THAT ARE BEING INDICATED ON SHEET |
| | M-1 EXISTING WATER AND SANITARY ISOMETRICS ARE NOT |
| | CLEARLY INDENTIFIED ON SHEET A-1 (P3, THREE HAND SINKS, |
| | WASHER). IF THESE FIXTURES ARE NOT ON THE NEW FLOOR |
| | PLAN THEY SHOULD BE DELETED TO AVOID FUTHER CONFUSION. |
| | PER FBC- PLUMBING SCTION 401.1 SCOPE, 601.1 SCOPE AND |
| | 701.1 SCOPE. |
| | |
| | 2. SHEET M-1 EXISTING WATER AND SANITARY ISOMETRICS. |
| | DELETE THE CLOUDED HAND SINK THAT STATES IT WAS OMITTED |
| | FROM THE DEMO PLAN. |
| | NOTE: THERE IS NO DEMO PLAN WITH THIS SET OF DRAWINGS |
| | AND THIS BEING ON THE PROPOSED PLANS IS CONFUSING. PER |
| | FBC - PLUMBING SECTION 601.1 SCOPE AND 701.1 SCOPE. |
| | |
| | 3. SHEETS A-1 AND M-1 ARE INDICATING AN EXISTING |
| | GREASE INTERCEPTOR IN SIDE OF THE RESTAURANT, HOWEVER |
| | THERE IS NO SIZE BEING INDICATED FOR THE INTERCEPTOR. |
| | CLEARLY INDICATE THE SIZE OF THE INTERCEPTOR. PER FBC- |
| | PLUMBING SECTION 701.1 SCOPE AND PLEASE PROVIDE THE |
| | FOLLOWING |
| | PER MUNICIPAL CODE ARTICLE III SECTION 90-124, THE |
| | EXISTING/PROPOSED GREASE INTERCEPTOR SHALL BE SIZED AND |
| | LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE |
| | UTILITY DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE: |
| | (561) 822-2272, E-MAIL: [email protected] THE FAX NUMBER |
| | IS (561) 822-2287. NOTE: WRITTEN APPROVAL IS REQUIRED |
| | OF THE EXISTING/PROPOSED GREASE INTERCEPTOR FROM |
| | ENVIRONMENTAL COMPLIANCE BEFORE A PERMIT CAN BE |
| | ISSUED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |