Plan Review Notes
Plan Review Notes For Permit 08060046
Permit Number 08060046
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-06-12 15:05:04***DENIED***
  
 1) PROVIDE LAYOUT OF FIRE SPRINKLER SYSTEM. IN
 ADDITION, SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED
 FOR FIRE SPRINKLER SYSTEM PRIOR TO INSTALLATION OF
 EQUIPMENT.
  
 2) DOES THE DISTANCE BETWEEN THE TWO EXITS IN THE
 DINING ROOM MEET THE REQUIREMENTS OF NFPA 101, SEC.
 7.5.1.3.3?
  
 3) PANEL LAYOUT REFERENCES A HOOD SUPPLY FAN. IS THAT
 EQUIPMENT A GREASE HOOD OR AN EXHAUST FAN FOR THE
 INVECTION OVEN? PLEASE CLARIFY
  
 4) 2A-10B,C RATED FIRE EXTINGUISHER(S) REQUIRED.
  
 5) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 6) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756