| 2008-06-10 14:27:32 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC CHAPTER 1 AS |
| | AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: ALL |
| | COMMENTS RELATE TO SHEET E-1 UNLESS OTHERWISE NOTED. |
| | |
| | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 |
| | FS, RESPECTIVELY. |
| | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, |
| | IF EXEMPTIONS APPLY. |
| | |
| | 2} THIS PROJECT MUST COMPLY WITH CHAPTER 13 FBC. SEE |
| | 13-415.1ABC.1.1FOR TIME CLOCK REQUIREMENTS AND.FOR |
| | LIGHTING DENSITIES ALL THAT IS REQUIRED FOR THE |
| | ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE |
| | REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE |
| | CALCULATION PROCEDURES, GENERAL. |
| | THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR |
| | A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| | SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD |
| | DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE |
| | METHOD DESCRIBED IN SECTION 415.2.B.1.THE INSTALLED |
| | INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH |
| | SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR |
| | LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| | SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE |
| | DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF |
| | THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE |
| | DENSITY REQUIREMENTS.INDICATE WATTAGES ON THE FIXTURE |
| | SCHEDULE. |
| | |
| | 3} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBCSPACE |
| | CONTROLS FOR LIGHTING. |
| | |
| | 4} SHOW COMPLIANCE WITH210.63 HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT OUTLET A |
| | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND |
| | WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING, |
| | AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET |
| | SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE |
| | EQUIPMENT DISCONNECTING MEANS. THIS COMMENT IS IN |
| | REGARD TO THE ROOF CONDENSING UNITS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |