Plan Review Notes
Plan Review Notes For Permit 08060015
Permit Number 08060015
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-06 11:51:42 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC CHAPTER 1 AS AMENDED AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
  
 1} THE REFERENCE TO NFPA72. 1-5.2.6 IN THE BATTERY
 CALCULATION, SHEET FA-1, IS INCORRECT. PER NFPA-72,
 2002 (REFERENCED STANDARD FBC, RFBC), THE FOLLOWING
 SHOULD BE REFERENCED.
  
 11.6.2 HOUSEHOLD FIRE ALARM SYSTEMS. POWER FOR
 HOUSEHOLD FIRE ALARM SYSTEMS SHALL COMPLY WITH THE
 FOLLOWING REQUIREMENTS:
 (1) HOUSEHOLD FIRE ALARM SYSTEMS SHALL HAVE TWO
 INDEPENDENT POWER SOURCES CONSISTING OF A PRIMARY
 SOURCE THAT USES COMMERCIAL LIGHT AND POWER AND A
 SECONDARY SOURCE THAT CONSISTS OF A RECHARGEABLE
 BATTERY.
 (2) THE SECONDARY SOURCE SHALL BE CAPABLE OF OPERATING
 THE SYSTEM FOR AT LEAST 24 HOURS IN THE NORMAL
 CONDITION FOLLOWED BY 4 MINUTES OF ALARM.
 (3) LOW-POWER WIRELESS SYSTEMS SHALL COMPLY WITH THE
 PERFORMANCE CRITERIA OF SECTION6.16.
  
 2} 11.8.3.5 SPECIFIC LOCATION REQUIREMENTS. THE
 INSTALLATION OF SMOKE ALARMS AND SMOKE DETECTORS SHALL
 COMPLY WITH THE FOLLOWING REQUIREMENTS:
  
 (5) SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN A 914-MM (36-IN.) HORIZONTAL PATH FROM
 A DOOR TO A KITCHEN OR A BATHROOM CONTAINING A SHOWER
 OR TUB.
  
 3} IDENTIFY THE MANUFACTURER'S NAME AND MODEL NUMBER OF
 THE BATTERY TO BE USED , ON THE BATTERY CALCULATIONS.
 106.1.1FBC.
  
 4} THE ENGINEER WHOSE NAME APPEARS ON THE TITLE BLOCK
 MUST SIGN, DATE AND SEAL THE DOCUMENT. 61G15-23.002
 FAC.
  
 NOTE: THE OWNER BUILDER DISCLOSURE STATEMENT SUBMITTED
 WITH THE PLANS IS NOT APPLICABLE AS A LICENSED
 CONTRACTOR FILED THE APPLICATION. PLEASE BE ADVISED
 THAT AN OWNER/ BUILDER WOULD NOT BE ALLOWED TO APPLY
 FOR THIS WORK AS THE EXCEPTION IN489.103.7(B) IS NOT
 MET BECAUSE THE PROPERTY IS OWNED BY A CORPORATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH