2008-06-04 07:35:072004 FBC W/2007 REVISIONS
 INSTALL NEW WINDOWS AND SHUTTERS
  
 DENIED BY BUILDING
  
 1) THE NOA SUBMITTED FOR THE TRACO 2100 WINDOWS IS
 EXPIRED. PLEASE SUBMIT A CURRENT NOA FOR THE WINDOWS.
 DCA RULE 9B-72.
  
 2) THE NEGATIVE WIND LOAD PRESSURE FOR THE 37 X 50
 WINDOW IS SPECIFIED ON THE PLANS AS -55.81 PSF. THE
 WINDOW THAT IS HIGHLITED ON THE NOA HAS A NEGATIVE
 DESIGN PRESSURE OF -54.12 FOR THIS WINDOW, WHICH IS TOO
 LOW. PLEASE CORRECT.
  
 3) THE STORM SHUTTER INSTALLATION SCHEDULE LISTS A
 SHUTTER SPAN OF 720" FOR OPENING W3, WHICH APPEARS TO
 BE INCORRECT. PLEASE REVIEW.
  