Plan Review Notes
Plan Review Notes For Permit 08050795
Permit Number 08050795
Review Stop P
Sequence Number 1
Notes
Date Text
2008-07-10 10:20:09DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH URBAN DESIGN STUDIO TITLE BLOCKS
 SHALL HAVE THE BUSINESS LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION NUMBER) INCLUDED IN THE TITLE BLOCK OF
 EACH SHEET. FAC 61G1-16.002(2) & FS 481.219.
  
 2. SHTS 1 OF 1 SITE PLAN & SHTS 1 THRU 4 OF 4 HARDSCAPE
 ARE NOT SIGNED, SEALED & DATED AS REQUIRED. SECTION
 106.1, FAC 61G1-16.003 & FS 481.306.
  
 3. SHTS 1 OF 2 IRRIGATION SHOW THE LOCATION OF THE
 CONTROLLER AND THE RAIN SENSOR. SECTION 106.1.2 & FS
 373.62.
  
 4. SHTS 1 & 2 OF 2 IRRIGATION THE PRINTED NAME OF THE
 LANDSCAPE ARCHITECT IS REQUIRED IN THE TITLE BLOCK OF
 EACH SHEET. FAC 61G1-16.002(6) & FS 481.306.
  
 5. SHT 1 OF 1 UPLIGHTING PLAN IS NOT SIGNED, SEALED AND
 DATED AS REQUIRED IN SECTION 106.1, FAC 61G1-16.003 &
 FS 481.306.
  
 6. SHT 1 OF 15 SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLES 1004.1.2 & 403.1. INDICATE IF
 EACH SPACE IS CONSENTRATED, STANDING SPACE OR
 UNCONSENTRATED. (EDUCATIONAL - MEETING ROOMS - WORKROOM
 - MULTIPURPOSE COMMUNITY ROOM). THE OCCUPANCY INDICATED
 372 & 216 SHALL BE VERIFIED.
  
 7. PER OCCUPANT LOAD INDICATED, (588 FOR BOTH FLOORS),
 3 DRINKING FOUNTAINS ARE REQUIRED. TABLE 403.1. ONLY
 TWO ARE SHOWN, (IF THE HIGH LOW HAS SEPARATE TRAPS AND
 WATER SUPPLIES). PLEASE SHOW THE LOCATION OF THE THIRD
 DRINKING FOUNTAIN. (ALSO SEE SECTION 410.1). AT LEAST
 50% OF ALL DRINKING FOUNTAINS PROVIDED SHALL BE
 ACCESSIBLE PER SECTION 11-4.1.3(10)(B).
  
 8. A GREASE INTERCEPTOR IS INDICATED. THE SIZING OF THE
 GREASE INTERCEPTOR SHALL BE BY THE UTILITY DEPT. PLEASE
 CONTACT RODNEY COMPO, ENVIRONMENTAL COMPLIANCE AT (561)
 644-1821, FAX (561) 822-2287 OR E-MAIL [email protected].
 ARTICLE III SECTION 90-124(7)
  
 9. SHT P101 SHOWS TYP 3/P201 FOR CONDENSATE. PLEASE
 INDICATE WHERE THE CONDENSATE DRAINS TO AS IT CAN NOT
 CAUSE A NUISANCE AND CAN NOT DRAIN ON TO A SIDEWALK,
 DRIVEWAY ETC. SECTIONS 106.1.2 & 314.2.1.
  
 10. SHT P301 EQUIPMENT & FIXTURES UTILIZED FOR THE
 STORAGE, PREP & HANDLING OF FOOD SHALL DISCHARGE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
 SECTION 802.1.1. A FLOOR SINK WILL BE REQUIRED PER
 SECTION 802.3.2.
  
 11. SHT P401 SANITARY RISER DIAGRAM, THE FLOOR DRAIN IN
 TOILET ROOM 223 IS NOT VENTED. SECTION 901.2.1.
  
 12. SHT P401 SANITARY RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN AS THERE ARE OFFSETS IN THE PIPING SHOWN
 ON THE FLOOR PLAN THAT ARE NOT SHOWN ON THE RISER
 DIAGRAM AS WELL ASTHE BASE OF THE STACK TO TOILET
 ROOMS 223 & 224 DOES NOT REFLECT THE FLOOR PLAN. (RISER
 TURNS SOUTH & FLOOR PLAN TURNS NORTH). SECTION 106.1.1.
 PLEASE CORRELATE.
  
 13. SHT P401 CONDENSATE RISER DIAGRAM THE PIPE SIZES DO
 NOT REFLECT THE FLOOR PLAN IN MANY AREAS. PLEASE
 CORRELATE AND SHOW ALL PIPE SIZES. ALSO THE CONDENSATE
 LINE DOWNSTREAM OF UNIT 1FC:6 IS SHOWN CONNECTING TO
 THE 2ND FLOOR CONDENSATE RISER ON THE RISER BUT NOT ON
 THE FLOOR PLAN. SECTION 106.1.1 & 314.
  
 14. SHT P401 WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN IN ABOUT 7 OR 8 AREAS. THE STUB-OUTS FOR THE
 FIXTURES IN THE GANG BATHS ARE SHOWN TURNING THE WRONG
 WAY, (AWAY FROM THE FIXTURES), AND PIPING THE THE
 CEILING FOR BRANCH CONNECTIONS TO THE WATER MAINS DOES
 NOT RELFECT IN SOME AREAS. THE DRINKING FOUNTAIN
 SUPPLIES ARE NOT SHOWN ON THE RISER AS WELL AS THE
 SUPPLY LINES TO THE SHOWER AND A "BS" FOR THE SECOND
 FLOOR. SECTIONS 106.1.1 & 601.1.
  
 15. SHT P401 WATER RISER DIAGRAM WATER HAMMER ARRESTORS
 ARE REQUIRED AT THE DISHWASHER & ICE MACHINE. SECTION
 604.9.
  
 16. SHT P401 WATER RISER DIAGRAM SHUT OFF VALVES ARE
 REQUIRED ON THE SUPPLY LINES TO EACH HOSE BIBB. SECTION
 606.2(2)
  
 17. SHT P401 WATER RISER DIAGRAM FULL OPEN VALVES ARE
 REQUIRED ON THE SUPPLY LINES TO EACH WATER HEATER.
 SECTION 606.1(7).
  
 18. SHT P401 WATER RISER DIAGRAM SHOW ALL PIPE SIZES.
 SECTION 604.1.
  
 19.SHT KP101 SANITARY FLOOR PLAN AND RISER DIAGRAM DOES
 NOT REFLECT THE PLUMBING LAYOUT AND RISER DIAGRAM ON
 SHTS P301 & P401. PLEASE CORRELATE. SECTION 106.1.1
  
 20 SHT KP102 KITCHEN WATER RISER WATER HAMMER ARRESTORS
 ARE REQUIRED AT THE DISHWASHER. SECTION 604.9. A SHUT
 OFF VALVE ARE REQUIRED AT THE HOSE BIBB SUPPLYLINE
 AND A FULL OPEN VALVE IS REQUIRED ON THE SUPPLY LINE TO
 THE WATER HEATER. SECTIONS 606.2(2) & 606.1(7).
  
 21. SHT KP103 A SEPARATE GAS PERMIT IS REQUIRED. PLEASE
 SUPPLY THE FOLLOWING INFORMATION FOR GAS PERMIT
 APPROVAL:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (CUT SECTIONS FROM THE METER TO THE
 FIRST RISER, AND THE DROP WITH THE VALVES AND UNIONS DO
 NOT INDICATE THE LENGTHS).
  
 B. TYPE OF GAS, (LP OR NATURAL).
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). (NOT ALL BTU LOADS ARE INDICATED ON THE
 RISER OR IN THE GAS REQUIREMENTS CHART).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN
 COMMENT "21-A" ADDRESSED).
  
 E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 F. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 G. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 H. GAS REQUIREMENT CHART DOES NOT REFLECT THE GAS RISER
 DIAGRAM. ONLY 4 APPLIANCES ARE SHOWN ON THE CHART, A,
 C, D & ONE NON DESIGNATED APPLIANCE. THE RISER SHOWS 5
 APPLIANCES, A, B, D, S & ONE NON DESIGNATED APPLIANCE
 WITH NO BTU LOAD INDICATED. PLEASE CORRELATE AND SHOW
 ALL BTU LOADS THAT REFLECT THE MANUF. SPECIFICATION
 SHEETS SUBMITTED. SECTIONS 106.1.1 & 402.
  
 I. GAS RISER DELETE THE UNION UPSTREAM OF THE MANUAL
 SHUT OFF VALVE AS IT IS NOT REQUIRED OR MOVE IT
 DOWNSTREAM OF THE MANUAL SHUT OFF VALVE.--MINIMUM
 1" STUB OUT AND SHUT OFF VALVE IS REQUIRED TO THE
 RANGE, APPLIANCE "A".--INDICATE THE MATERIAL FOR
 THE VENT FOR THE SECOND STAGE REGULATOR. (SHALL BE NON
 COMBUSTABLE).
 SECTION 403.6. (SEE NFPA 54 SECTIONS 5.8.5.1 & 6.4).
  
 22. SHT KD101 DETAIL 8 WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASH MACHINE. SECTION 604.9.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved