| Date |
Text |
| 2008-07-10 10:20:09 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | CITY WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL SHEETS WITH URBAN DESIGN STUDIO TITLE BLOCKS |
| | SHALL HAVE THE BUSINESS LICENSE NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION NUMBER) INCLUDED IN THE TITLE BLOCK OF |
| | EACH SHEET. FAC 61G1-16.002(2) & FS 481.219. |
| | |
| | 2. SHTS 1 OF 1 SITE PLAN & SHTS 1 THRU 4 OF 4 HARDSCAPE |
| | ARE NOT SIGNED, SEALED & DATED AS REQUIRED. SECTION |
| | 106.1, FAC 61G1-16.003 & FS 481.306. |
| | |
| | 3. SHTS 1 OF 2 IRRIGATION SHOW THE LOCATION OF THE |
| | CONTROLLER AND THE RAIN SENSOR. SECTION 106.1.2 & FS |
| | 373.62. |
| | |
| | 4. SHTS 1 & 2 OF 2 IRRIGATION THE PRINTED NAME OF THE |
| | LANDSCAPE ARCHITECT IS REQUIRED IN THE TITLE BLOCK OF |
| | EACH SHEET. FAC 61G1-16.002(6) & FS 481.306. |
| | |
| | 5. SHT 1 OF 1 UPLIGHTING PLAN IS NOT SIGNED, SEALED AND |
| | DATED AS REQUIRED IN SECTION 106.1, FAC 61G1-16.003 & |
| | FS 481.306. |
| | |
| | 6. SHT 1 OF 15 SUBMIT CALCULATIONS FOR MINIMUM |
| | FACILITIES PER TABLES 1004.1.2 & 403.1. INDICATE IF |
| | EACH SPACE IS CONSENTRATED, STANDING SPACE OR |
| | UNCONSENTRATED. (EDUCATIONAL - MEETING ROOMS - WORKROOM |
| | - MULTIPURPOSE COMMUNITY ROOM). THE OCCUPANCY INDICATED |
| | 372 & 216 SHALL BE VERIFIED. |
| | |
| | 7. PER OCCUPANT LOAD INDICATED, (588 FOR BOTH FLOORS), |
| | 3 DRINKING FOUNTAINS ARE REQUIRED. TABLE 403.1. ONLY |
| | TWO ARE SHOWN, (IF THE HIGH LOW HAS SEPARATE TRAPS AND |
| | WATER SUPPLIES). PLEASE SHOW THE LOCATION OF THE THIRD |
| | DRINKING FOUNTAIN. (ALSO SEE SECTION 410.1). AT LEAST |
| | 50% OF ALL DRINKING FOUNTAINS PROVIDED SHALL BE |
| | ACCESSIBLE PER SECTION 11-4.1.3(10)(B). |
| | |
| | 8. A GREASE INTERCEPTOR IS INDICATED. THE SIZING OF THE |
| | GREASE INTERCEPTOR SHALL BE BY THE UTILITY DEPT. PLEASE |
| | CONTACT RODNEY COMPO, ENVIRONMENTAL COMPLIANCE AT (561) |
| | 644-1821, FAX (561) 822-2287 OR E-MAIL [email protected]. |
| | ARTICLE III SECTION 90-124(7) |
| | |
| | 9. SHT P101 SHOWS TYP 3/P201 FOR CONDENSATE. PLEASE |
| | INDICATE WHERE THE CONDENSATE DRAINS TO AS IT CAN NOT |
| | CAUSE A NUISANCE AND CAN NOT DRAIN ON TO A SIDEWALK, |
| | DRIVEWAY ETC. SECTIONS 106.1.2 & 314.2.1. |
| | |
| | 10. SHT P301 EQUIPMENT & FIXTURES UTILIZED FOR THE |
| | STORAGE, PREP & HANDLING OF FOOD SHALL DISCHARGE |
| | THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP. |
| | SECTION 802.1.1. A FLOOR SINK WILL BE REQUIRED PER |
| | SECTION 802.3.2. |
| | |
| | 11. SHT P401 SANITARY RISER DIAGRAM, THE FLOOR DRAIN IN |
| | TOILET ROOM 223 IS NOT VENTED. SECTION 901.2.1. |
| | |
| | 12. SHT P401 SANITARY RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN AS THERE ARE OFFSETS IN THE PIPING SHOWN |
| | ON THE FLOOR PLAN THAT ARE NOT SHOWN ON THE RISER |
| | DIAGRAM AS WELL ASTHE BASE OF THE STACK TO TOILET |
| | ROOMS 223 & 224 DOES NOT REFLECT THE FLOOR PLAN. (RISER |
| | TURNS SOUTH & FLOOR PLAN TURNS NORTH). SECTION 106.1.1. |
| | PLEASE CORRELATE. |
| | |
| | 13. SHT P401 CONDENSATE RISER DIAGRAM THE PIPE SIZES DO |
| | NOT REFLECT THE FLOOR PLAN IN MANY AREAS. PLEASE |
| | CORRELATE AND SHOW ALL PIPE SIZES. ALSO THE CONDENSATE |
| | LINE DOWNSTREAM OF UNIT 1FC:6 IS SHOWN CONNECTING TO |
| | THE 2ND FLOOR CONDENSATE RISER ON THE RISER BUT NOT ON |
| | THE FLOOR PLAN. SECTION 106.1.1 & 314. |
| | |
| | 14. SHT P401 WATER RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN IN ABOUT 7 OR 8 AREAS. THE STUB-OUTS FOR THE |
| | FIXTURES IN THE GANG BATHS ARE SHOWN TURNING THE WRONG |
| | WAY, (AWAY FROM THE FIXTURES), AND PIPING THE THE |
| | CEILING FOR BRANCH CONNECTIONS TO THE WATER MAINS DOES |
| | NOT RELFECT IN SOME AREAS. THE DRINKING FOUNTAIN |
| | SUPPLIES ARE NOT SHOWN ON THE RISER AS WELL AS THE |
| | SUPPLY LINES TO THE SHOWER AND A "BS" FOR THE SECOND |
| | FLOOR. SECTIONS 106.1.1 & 601.1. |
| | |
| | 15. SHT P401 WATER RISER DIAGRAM WATER HAMMER ARRESTORS |
| | ARE REQUIRED AT THE DISHWASHER & ICE MACHINE. SECTION |
| | 604.9. |
| | |
| | 16. SHT P401 WATER RISER DIAGRAM SHUT OFF VALVES ARE |
| | REQUIRED ON THE SUPPLY LINES TO EACH HOSE BIBB. SECTION |
| | 606.2(2) |
| | |
| | 17. SHT P401 WATER RISER DIAGRAM FULL OPEN VALVES ARE |
| | REQUIRED ON THE SUPPLY LINES TO EACH WATER HEATER. |
| | SECTION 606.1(7). |
| | |
| | 18. SHT P401 WATER RISER DIAGRAM SHOW ALL PIPE SIZES. |
| | SECTION 604.1. |
| | |
| | 19.SHT KP101 SANITARY FLOOR PLAN AND RISER DIAGRAM DOES |
| | NOT REFLECT THE PLUMBING LAYOUT AND RISER DIAGRAM ON |
| | SHTS P301 & P401. PLEASE CORRELATE. SECTION 106.1.1 |
| | |
| | 20 SHT KP102 KITCHEN WATER RISER WATER HAMMER ARRESTORS |
| | ARE REQUIRED AT THE DISHWASHER. SECTION 604.9. A SHUT |
| | OFF VALVE ARE REQUIRED AT THE HOSE BIBB SUPPLYLINE |
| | AND A FULL OPEN VALVE IS REQUIRED ON THE SUPPLY LINE TO |
| | THE WATER HEATER. SECTIONS 606.2(2) & 606.1(7). |
| | |
| | 21. SHT KP103 A SEPARATE GAS PERMIT IS REQUIRED. PLEASE |
| | SUPPLY THE FOLLOWING INFORMATION FOR GAS PERMIT |
| | APPROVAL: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. (CUT SECTIONS FROM THE METER TO THE |
| | FIRST RISER, AND THE DROP WITH THE VALVES AND UNIONS DO |
| | NOT INDICATE THE LENGTHS). |
| | |
| | B. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). (NOT ALL BTU LOADS ARE INDICATED ON THE |
| | RISER OR IN THE GAS REQUIREMENTS CHART). |
| | |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). (TO BE VERIFIED WHEN |
| | COMMENT "21-A" ADDRESSED). |
| | |
| | E. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | F. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | G. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | H. GAS REQUIREMENT CHART DOES NOT REFLECT THE GAS RISER |
| | DIAGRAM. ONLY 4 APPLIANCES ARE SHOWN ON THE CHART, A, |
| | C, D & ONE NON DESIGNATED APPLIANCE. THE RISER SHOWS 5 |
| | APPLIANCES, A, B, D, S & ONE NON DESIGNATED APPLIANCE |
| | WITH NO BTU LOAD INDICATED. PLEASE CORRELATE AND SHOW |
| | ALL BTU LOADS THAT REFLECT THE MANUF. SPECIFICATION |
| | SHEETS SUBMITTED. SECTIONS 106.1.1 & 402. |
| | |
| | I. GAS RISER DELETE THE UNION UPSTREAM OF THE MANUAL |
| | SHUT OFF VALVE AS IT IS NOT REQUIRED OR MOVE IT |
| | DOWNSTREAM OF THE MANUAL SHUT OFF VALVE.--MINIMUM |
| | 1" STUB OUT AND SHUT OFF VALVE IS REQUIRED TO THE |
| | RANGE, APPLIANCE "A".--INDICATE THE MATERIAL FOR |
| | THE VENT FOR THE SECOND STAGE REGULATOR. (SHALL BE NON |
| | COMBUSTABLE). |
| | SECTION 403.6. (SEE NFPA 54 SECTIONS 5.8.5.1 & 6.4). |
| | |
| | 22. SHT KD101 DETAIL 8 WATER HAMMER ARRESTORS ARE |
| | REQUIRED AT THE WASH MACHINE. SECTION 604.9. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |