2008-06-25 09:49:35REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PG LS-1: ACCORDING TO THE LIFE SAFETY SYMBOL LEGEND,
 THIS FLOOR PLAN SHOWS DUCT MOUNTED SMOKE DETECTORS
 THROUGHOUT THE BUILDING (INDICATED BY THE SMALL ?S?
 NEXT TO THE SMOKE DETECTOR SYMBOL). NO SUCH DETECTORS
 ARE SHOWN ON MECHANICAL FLOOR PLANS. PLEASE CLARIFY AND
 COORDINATE DRAWINGS, SHOWING COMPLIANCE WITH FBCM
 606.3.
 NOTE: THIS COMMENT IS NOT INTENDED TO DETERMINE WHETHER
 OR NOT DUCT DETECTORS ARE REQUIRED. SEE FBCM 606.2 FOR
 REQUIREMENTS.
  
 2. PAGE LS-1 USES SYMBOLS SUCH AS SR AND 1F TO LABEL
 SOME WALLS. THERE IS NO INDICATION ON THE SYMBOL LEGEND
 WHAT THESE SYMBOLS REPRESENT. IF IT IS ASSUMED THAT 1F
 INDICATES A 1-HOUR FIRE RESISTANT WALL, THIS CAN NOT BE
 CONFIRMED WITH ARCHITECTURAL FLOOR PLANS AS SOME OF THE
 WALLS WITH THE 1F DESIGNATION ARE NOT SHOWN TO BE FIRE
 RESISTANCE RATED ON ARCHITECTURAL FLOOR PLANS. EXAMPLE:
 THE WALLS OF CORRIDOR 205 ARE MARKED WITH THE 1F
 DESIGNATION BUT ARE SHOWN AS WALL TYPE P4. ACCORDING TO
 WALL SCHEDULE ON A-12 THIS WALL TYPE CARRIES NO RATING.
 AS A RESULT, THE APPROPRIATE REQUIRED PROTECTION OF
 DUCT PENETRATIONS AT WALL ASSEMBLIES CAN NOT BE
 DETERMINED. A THOROUGH REVIEW OF DUCT PLANS CAN NOT BE
 PERFORMED AT THIS TIME.
  
 3. PAGE M101: 1FC:# SHOWS A DUCT SMOKE DETECTOR ON THE
 RETURN AIR SIDE. DUCT SMOKE DETECTORS SHALL BE
 INSTALLED ON THE SUPPLY SIDE IN ACCORDANCE WITH FBCM
 606.2.1.
  
 4. PAGES M101 AND M102: KEY NOTE #3 CALLS FOR CO2
 DETECTORS TO CONTROL MODULATING DAMPERS, BUT KEY NOTE
 #4 CALLS FOR THE CO2 DETECTORS TO CONTROL THE FCUS.
 PLEASE CLARIFY DESIGN INTENT AND NOTES TO ELIMINATE
 CONFLICTING INFORMATION AND SHOW COMPLIANCE WITH FBCM
 401.3 AND 403.4.
  
 5. PAGE M101: OUTSIDE AIR INTAKES FOR ERVS DO NOT SHOW
 MOTORIZED DAMPERS ON PLAN. OUTDOOR AIR SUPPLY SYSTEMS
 SHALL BE EQUIPPED WITH MOTORIZED DAMPERS THAT WILL
 AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES SERVED
 ARE NOT IN USE IN ACCORDANCE WITH FBCB
 13-409.1.ABC.3.3.
  
 6. PAGE M102: THIS BUILDING IS DECLARED AS AN A-3
 OCCUPANCY ON PAGE LS-1. EXIT ACCESS CORRIDORS ARE
 REQIRED TO BE MINIMUM 1-HOUR FIRE RESISTANCE RATED IN
 ACCORDANCE WITH FBCB TABLE 1016.1. DUCTS AND AIR
 TRANSFER OPENINGS WHICH PENETRATE THE WALLS OF CORRIDOR
 205 SHALL BE PROTECTED WITH FIRE AND SMOKE DAMPERS IN
 ACCORDANCE WITH FBCM 607.5 AND 607.5.4. SEE ALSO FBCB
 715.3.3. CHECK ALL DUCT PENETRATIONS IN THIS AREA FOR
 COMPLIANCE. ALSO, SHOW HOW SMOKE DAMPERS ARE TO BE
 ACTUATED IN ACCORDANCE WITH FBCM 607.5.4.1.
  
 7. PAGE M102: KITCHEN EXHAUST GREASE DUCT IS SHOWN
 PENETRATING FLOOR/CEILING ASSEMBLY. WHILE PLANS CALL
 FOR THE GREASE DUCT TO BE FIRE-WRAPPED, THERE IS NO
 INDICATION ON PLANS AS TO HOW THE FLOOR/CEILING
 PENETRATION IS TO BE PROTECTED. ARCHITECTURAL PLANS
 SHOW AN ENCLOSURE AROUND THE DUCT ON 2ND FLOOR BUT NO
 RATING OF THE ENCLOSURE. PLEASE SHOW HOW THIS
 PENETRATION IS TO BE PROTECTED IN ACCORDANCE WITH FBCM
 607.6.
  
 8. PAGE M102: THE 12X12 SUPPLY DUCT FROM 2FC:1 IS SHOWN
 PENETRATING A 1-HOUR FIRE RESISTANCE RATED WALL WITHOUT
 ANY PROTECTION OF THE PENETRATION. SHOW HOW THIS DUCT
 PENETRATION IS TO BE PROTECTED IN ACCORDANCE WITH FBCM
 607.5. SEE ALSO COMMENT #6 ABOVE.
  
 9. PAGE M102: THE SIZE OF THE RETURN DUCT SERVING ROOM
 218 IS MISSING SIZE AND GRILL DESIGNATION. PLEASE
 CLARIFY. AN AIR DISTRIBUTION SYSTEM SHALL BE DESIGNED
 AND INSTALLED TO SUPPLY THE REQUIRED DISTRIBUTION OF
 AIR IN ACCORDANCE WITH FBCM 603.1.
  
 10. PAGE M202 DETAILS FOR ALL ROOF MOUNTED AND OUTDOOR
 EQUIPMENT AND APPLIANCES: NO INFORMATION WAS PROVIDED
 IN STRUCTURAL OR MECHANICAL PLANS REGARDING WIND
 RESISTANCE. PROVIDE SPECIFIC ATTACHMENT DETAIL FOR ROOF
 CURBS AND A/C STANDS TO THE BUILDING STRUCTURE AS WELL
 AS FOR APPLIANCE ATTACHMENT TO CURBS AND STANDS WITH
 SUPPORTING WIND LOAD CALCULATIONS IN ACCORDANCE WITH
 FBCM 301.13 AND FBCB SECTION 1609. ALSO, PROVIDE
 DOCUMENTATION SHOWING APPLIANCES (SUCH AS THE GREASE
 EXHAUST FAN, FOR EXAMPLE) ARE DESIGNED TO RESIST WIND
 PRESSURES IN ACCORDANCE WITH THESE SECTIONS.
  
 11. PAGE M202 FAN COIL CONDENSATE DRAIN DETAIL:
 AUXILIARY OR SECONDARY DRAIN PROTECTION IS REQUIRED AT
 ALL COILS WHICH PRODUCE CONDENSATE IN ACCORDANCE WITH
 FBCM 307.2.3. THE DETAIL SHOWS A FLOAT SWITCH INSTALLED
 IN THE PRIMARY CONDENSATE DRAIN LINE. THIS IS NOT ONE
 OF THE METHODS ACCEPTED UNDER THIS SECTION. THE FLOAT
 SWITCH MAY BE INSTALLED IN AN AUXILIARY DRAIN PAN, ON A
 SECONDARY DRAIN LINE OR INSIDE THE FAN COIL ON THE
 PRIMARY DRAIN PAN TO SHOW COMPLIANCE WITH THE
 REQUIREMENTS OF THIS SECTION.
  
 12. PAGE M202 FIRE DAMPER DETAIL: FIRE AND SMOKE
 DAMPERS SHALL BE INSTALLED IN ACCORDANCE WITH THEIR
 LISTING AND MANUFACTURER?S INSTALLATION INSTRUCTIONS
 PER FBCM 607.2. PROVIDE A DETAIL WHICH CORRESPONDS WITH
 THE DAMPERS BEING USED OR PROVIDE MANUFACTURER?S
 INSTRUCTIONS.
  
 13. PAGE M301. WHAT IS THE HEIGHT OF KEF-1 IN RELATION
 TO THE PARAPET WALLS SURROUNDING THIS ROOF AREA?
 ACCORDING TO THE ELEVATIONS SHOWN ON PAGE A-3, THE
 PARAPET IS APPROXIMATELY 8 FEET ABOVE THE MECHANICAL
 ROOF LEVEL. EXHAUST OUTLETS SHALL BE LOCATED NOT LESS
 THAN 10 FEET (3048 MM) HORIZONTALLY FROM PARTS OF THE
 SAME OR CONTIGUOUS BUILDINGS (INCLUDING PARAPETS) IN
 ACCORDANCE WITH FBCM 506.3.12.3. EXHAUST FANS SHALL BE
 POSITIONED SO THAT THE DISCHARGE WILL NOT IMPINGE ON
 THE ROOF, OTHER EQUIPMENT OR APPLIANCES OR PARTS OF THE
 STRUCTURE IN ACCORDANCE WITH FBCM 506.5.2. THE MINIMUM
 HORIZONTAL DISTANCE BETWEEN VERTICAL DISCHARGE FANS AND
 PARAPET-TYPE BUILDING STRUCTURES SHALL BE 2 FEET
 PROVIDED THAT SUCH STRUCTURES ARE NOT HIGHER THAN THE
 TOP OF THE FAN DISCHARGE OPENING IN ACCORDANCE WITH
 FBCM 506.5.5. PROVIDE SUFFICIENT DETAILS IN PLAN AND
 ELEVATION VIEW TO SHOW COMPLIANCE WITH THESE SECTIONS.
  
 14. ENERGY CALCULATIONS CAN NOT BE REVIEWED AT THIS
 TIME AS THE INPUT DATA REPORT WAS NOT INCLUDED WITH THE
 COMPLIANCE REPORT. PLEASE SEE PAGE TWO OF THE
 COMPLIANCE REPORT WHICH STATES: IMPORTANT NOTE: AN
 INPUT REPORT OF THIS DESIGN BUILDING MUST BE SUBMITTED
 ALONG WITH THIS COMPLIANCE REPORT.
  