| 2008-06-25 09:49:35 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PG LS-1: ACCORDING TO THE LIFE SAFETY SYMBOL LEGEND, |
| | THIS FLOOR PLAN SHOWS DUCT MOUNTED SMOKE DETECTORS |
| | THROUGHOUT THE BUILDING (INDICATED BY THE SMALL ?S? |
| | NEXT TO THE SMOKE DETECTOR SYMBOL). NO SUCH DETECTORS |
| | ARE SHOWN ON MECHANICAL FLOOR PLANS. PLEASE CLARIFY AND |
| | COORDINATE DRAWINGS, SHOWING COMPLIANCE WITH FBCM |
| | 606.3. |
| | NOTE: THIS COMMENT IS NOT INTENDED TO DETERMINE WHETHER |
| | OR NOT DUCT DETECTORS ARE REQUIRED. SEE FBCM 606.2 FOR |
| | REQUIREMENTS. |
| | |
| | 2. PAGE LS-1 USES SYMBOLS SUCH AS SR AND 1F TO LABEL |
| | SOME WALLS. THERE IS NO INDICATION ON THE SYMBOL LEGEND |
| | WHAT THESE SYMBOLS REPRESENT. IF IT IS ASSUMED THAT 1F |
| | INDICATES A 1-HOUR FIRE RESISTANT WALL, THIS CAN NOT BE |
| | CONFIRMED WITH ARCHITECTURAL FLOOR PLANS AS SOME OF THE |
| | WALLS WITH THE 1F DESIGNATION ARE NOT SHOWN TO BE FIRE |
| | RESISTANCE RATED ON ARCHITECTURAL FLOOR PLANS. EXAMPLE: |
| | THE WALLS OF CORRIDOR 205 ARE MARKED WITH THE 1F |
| | DESIGNATION BUT ARE SHOWN AS WALL TYPE P4. ACCORDING TO |
| | WALL SCHEDULE ON A-12 THIS WALL TYPE CARRIES NO RATING. |
| | AS A RESULT, THE APPROPRIATE REQUIRED PROTECTION OF |
| | DUCT PENETRATIONS AT WALL ASSEMBLIES CAN NOT BE |
| | DETERMINED. A THOROUGH REVIEW OF DUCT PLANS CAN NOT BE |
| | PERFORMED AT THIS TIME. |
| | |
| | 3. PAGE M101: 1FC:# SHOWS A DUCT SMOKE DETECTOR ON THE |
| | RETURN AIR SIDE. DUCT SMOKE DETECTORS SHALL BE |
| | INSTALLED ON THE SUPPLY SIDE IN ACCORDANCE WITH FBCM |
| | 606.2.1. |
| | |
| | 4. PAGES M101 AND M102: KEY NOTE #3 CALLS FOR CO2 |
| | DETECTORS TO CONTROL MODULATING DAMPERS, BUT KEY NOTE |
| | #4 CALLS FOR THE CO2 DETECTORS TO CONTROL THE FCUS. |
| | PLEASE CLARIFY DESIGN INTENT AND NOTES TO ELIMINATE |
| | CONFLICTING INFORMATION AND SHOW COMPLIANCE WITH FBCM |
| | 401.3 AND 403.4. |
| | |
| | 5. PAGE M101: OUTSIDE AIR INTAKES FOR ERVS DO NOT SHOW |
| | MOTORIZED DAMPERS ON PLAN. OUTDOOR AIR SUPPLY SYSTEMS |
| | SHALL BE EQUIPPED WITH MOTORIZED DAMPERS THAT WILL |
| | AUTOMATICALLY SHUT WHEN THE SYSTEMS OR SPACES SERVED |
| | ARE NOT IN USE IN ACCORDANCE WITH FBCB |
| | 13-409.1.ABC.3.3. |
| | |
| | 6. PAGE M102: THIS BUILDING IS DECLARED AS AN A-3 |
| | OCCUPANCY ON PAGE LS-1. EXIT ACCESS CORRIDORS ARE |
| | REQIRED TO BE MINIMUM 1-HOUR FIRE RESISTANCE RATED IN |
| | ACCORDANCE WITH FBCB TABLE 1016.1. DUCTS AND AIR |
| | TRANSFER OPENINGS WHICH PENETRATE THE WALLS OF CORRIDOR |
| | 205 SHALL BE PROTECTED WITH FIRE AND SMOKE DAMPERS IN |
| | ACCORDANCE WITH FBCM 607.5 AND 607.5.4. SEE ALSO FBCB |
| | 715.3.3. CHECK ALL DUCT PENETRATIONS IN THIS AREA FOR |
| | COMPLIANCE. ALSO, SHOW HOW SMOKE DAMPERS ARE TO BE |
| | ACTUATED IN ACCORDANCE WITH FBCM 607.5.4.1. |
| | |
| | 7. PAGE M102: KITCHEN EXHAUST GREASE DUCT IS SHOWN |
| | PENETRATING FLOOR/CEILING ASSEMBLY. WHILE PLANS CALL |
| | FOR THE GREASE DUCT TO BE FIRE-WRAPPED, THERE IS NO |
| | INDICATION ON PLANS AS TO HOW THE FLOOR/CEILING |
| | PENETRATION IS TO BE PROTECTED. ARCHITECTURAL PLANS |
| | SHOW AN ENCLOSURE AROUND THE DUCT ON 2ND FLOOR BUT NO |
| | RATING OF THE ENCLOSURE. PLEASE SHOW HOW THIS |
| | PENETRATION IS TO BE PROTECTED IN ACCORDANCE WITH FBCM |
| | 607.6. |
| | |
| | 8. PAGE M102: THE 12X12 SUPPLY DUCT FROM 2FC:1 IS SHOWN |
| | PENETRATING A 1-HOUR FIRE RESISTANCE RATED WALL WITHOUT |
| | ANY PROTECTION OF THE PENETRATION. SHOW HOW THIS DUCT |
| | PENETRATION IS TO BE PROTECTED IN ACCORDANCE WITH FBCM |
| | 607.5. SEE ALSO COMMENT #6 ABOVE. |
| | |
| | 9. PAGE M102: THE SIZE OF THE RETURN DUCT SERVING ROOM |
| | 218 IS MISSING SIZE AND GRILL DESIGNATION. PLEASE |
| | CLARIFY. AN AIR DISTRIBUTION SYSTEM SHALL BE DESIGNED |
| | AND INSTALLED TO SUPPLY THE REQUIRED DISTRIBUTION OF |
| | AIR IN ACCORDANCE WITH FBCM 603.1. |
| | |
| | 10. PAGE M202 DETAILS FOR ALL ROOF MOUNTED AND OUTDOOR |
| | EQUIPMENT AND APPLIANCES: NO INFORMATION WAS PROVIDED |
| | IN STRUCTURAL OR MECHANICAL PLANS REGARDING WIND |
| | RESISTANCE. PROVIDE SPECIFIC ATTACHMENT DETAIL FOR ROOF |
| | CURBS AND A/C STANDS TO THE BUILDING STRUCTURE AS WELL |
| | AS FOR APPLIANCE ATTACHMENT TO CURBS AND STANDS WITH |
| | SUPPORTING WIND LOAD CALCULATIONS IN ACCORDANCE WITH |
| | FBCM 301.13 AND FBCB SECTION 1609. ALSO, PROVIDE |
| | DOCUMENTATION SHOWING APPLIANCES (SUCH AS THE GREASE |
| | EXHAUST FAN, FOR EXAMPLE) ARE DESIGNED TO RESIST WIND |
| | PRESSURES IN ACCORDANCE WITH THESE SECTIONS. |
| | |
| | 11. PAGE M202 FAN COIL CONDENSATE DRAIN DETAIL: |
| | AUXILIARY OR SECONDARY DRAIN PROTECTION IS REQUIRED AT |
| | ALL COILS WHICH PRODUCE CONDENSATE IN ACCORDANCE WITH |
| | FBCM 307.2.3. THE DETAIL SHOWS A FLOAT SWITCH INSTALLED |
| | IN THE PRIMARY CONDENSATE DRAIN LINE. THIS IS NOT ONE |
| | OF THE METHODS ACCEPTED UNDER THIS SECTION. THE FLOAT |
| | SWITCH MAY BE INSTALLED IN AN AUXILIARY DRAIN PAN, ON A |
| | SECONDARY DRAIN LINE OR INSIDE THE FAN COIL ON THE |
| | PRIMARY DRAIN PAN TO SHOW COMPLIANCE WITH THE |
| | REQUIREMENTS OF THIS SECTION. |
| | |
| | 12. PAGE M202 FIRE DAMPER DETAIL: FIRE AND SMOKE |
| | DAMPERS SHALL BE INSTALLED IN ACCORDANCE WITH THEIR |
| | LISTING AND MANUFACTURER?S INSTALLATION INSTRUCTIONS |
| | PER FBCM 607.2. PROVIDE A DETAIL WHICH CORRESPONDS WITH |
| | THE DAMPERS BEING USED OR PROVIDE MANUFACTURER?S |
| | INSTRUCTIONS. |
| | |
| | 13. PAGE M301. WHAT IS THE HEIGHT OF KEF-1 IN RELATION |
| | TO THE PARAPET WALLS SURROUNDING THIS ROOF AREA? |
| | ACCORDING TO THE ELEVATIONS SHOWN ON PAGE A-3, THE |
| | PARAPET IS APPROXIMATELY 8 FEET ABOVE THE MECHANICAL |
| | ROOF LEVEL. EXHAUST OUTLETS SHALL BE LOCATED NOT LESS |
| | THAN 10 FEET (3048 MM) HORIZONTALLY FROM PARTS OF THE |
| | SAME OR CONTIGUOUS BUILDINGS (INCLUDING PARAPETS) IN |
| | ACCORDANCE WITH FBCM 506.3.12.3. EXHAUST FANS SHALL BE |
| | POSITIONED SO THAT THE DISCHARGE WILL NOT IMPINGE ON |
| | THE ROOF, OTHER EQUIPMENT OR APPLIANCES OR PARTS OF THE |
| | STRUCTURE IN ACCORDANCE WITH FBCM 506.5.2. THE MINIMUM |
| | HORIZONTAL DISTANCE BETWEEN VERTICAL DISCHARGE FANS AND |
| | PARAPET-TYPE BUILDING STRUCTURES SHALL BE 2 FEET |
| | PROVIDED THAT SUCH STRUCTURES ARE NOT HIGHER THAN THE |
| | TOP OF THE FAN DISCHARGE OPENING IN ACCORDANCE WITH |
| | FBCM 506.5.5. PROVIDE SUFFICIENT DETAILS IN PLAN AND |
| | ELEVATION VIEW TO SHOW COMPLIANCE WITH THESE SECTIONS. |
| | |
| | 14. ENERGY CALCULATIONS CAN NOT BE REVIEWED AT THIS |
| | TIME AS THE INPUT DATA REPORT WAS NOT INCLUDED WITH THE |
| | COMPLIANCE REPORT. PLEASE SEE PAGE TWO OF THE |
| | COMPLIANCE REPORT WHICH STATES: IMPORTANT NOTE: AN |
| | INPUT REPORT OF THIS DESIGN BUILDING MUST BE SUBMITTED |
| | ALONG WITH THIS COMPLIANCE REPORT. |
| | |