| 2008-07-17 16:06:01 | ***DENIED*** |
| | |
| | 1) PLEASE VERIFY CORRECT ADDRESS. PLANS INDICATE 814 |
| | DIVISION AVE. AND PERMIT APPLICATION SHOWS 706 8TH ST. |
| | |
| | 2) FIRE DEPARTMENT CONNECTION TO BE PROVIDED WITH KNOX |
| | LOCKING CAPS. CONTACT WEST PALM BEACH BUREAU OF FIRE |
| | PREVENTION AT (561( 804-4724 FOR APPLICATION. |
| | |
| | 3) KNOX BOX REQUIRED ON BUILDING FOR AFTER NORMAL |
| | BUSINESS HOURS ACCESS FOR EMERGENCIES. CONTACT WEST |
| | PALM BEACH BUREAU OF FIRE PREVENTION AT (561) 804-4724 |
| | FOR APPLICATION. |
| | |
| | 4) IN ADDITION TO ELECTRONIC SUPERVISION, DOUBLE CHECK |
| | DETECTOR ASSEMBLY TO BE SECURED WITH LOCK AND CHAIN. |
| | |
| | 5) PLEASE ADD NFPA 13, 2002 AND NFPA 72, 2002 TO |
| | BUILDING CODE ANALYSIS ON SHEET LS-1. |
| | |
| | 6) PROVIDE CALCULATION FOR TOTAL BUILDING OCCUPANT LOAD |
| | USING NFPA 101, TABLE 7.3.1.2. |
| | |
| | 7) CLARIFY DETECTION DEVICES SHOWN ON SHEET LS-1. ARE |
| | DEVICES AREA SMOKE DETECTORS OR DUCT SMOKE DETECTORS AS |
| | INDICATED IN LS SYMBOL LEGEND? NONE OF THESE DEVICES |
| | ARE INDICATED ON FIRE ALARM DRAWINGS. |
| | |
| | 8) SMOKE DETECTORS NOT SHOWN IN AREA OF FACP OR |
| | ELEVATOR LOBBY FIRST FLOOR ON LS-1. OK ON FIRE ALARM |
| | PLANS. PLEASE CORRELATE INFORMATION. |
| | |
| | 9) NO FIRE ALARM DEVICES ARE SHOWN IN MEETING ROOMS A |
| | AND B SECOND FLOOR ON SHEET LS-1. |
| | |
| | 10) STAIR #2 SHOULD BE CORRECTED TO READ FIRE SPRINKLER |
| | RISER. |
| | |
| | 11) PROVIDE MINIMUM STRENGTH REQUIREMENTS FOR GUARDS |
| | AND HANDRAILS. |
| | |
| | 12) ADDRESS IS REQUIRED ON BUILDING THAT SHALL BE A |
| | MINIMUM OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH |
| | BACKGROUND. PLEASE ADD TO ELEVATIONS. |
| | |
| | 13) STAIRS TO COMPLY WITH NFPA 101 SEC. 7.2.2. PLEASE |
| | CLARIFY WIDTH OF TREADS. |
| | |
| | 14) HANDRAILS ARE REQUIRED ON BOTH SIDES OF STAIRS. |
| | NFPA 101, SEC. 7.2.2.4.1.1. |
| | |
| | 15) THE DOOR SCHEDULE INDICATES CLOSERS ON SOME OF THE |
| | DOORS. SOME OF THE RATED DOORS ARE LISTED WITH NO |
| | CLOSERS. PLEASE EXPLAIN OR ADD TO SCHEDULE. |
| | |
| | 16) EQUIPMENT THAT COOKS FOOD CAPABLE OF PRODUCING |
| | GREASE LADEN VAPORS SHALL BE PROTECTED BY AN APPROVED |
| | HOOD/SUPPRESSION SYSTEM. THE SYSTEM SHALL BE TIED INTO |
| | THE FIRE ALARM AND SEPARATE SHOP DRAWINGS AND PERMITS |
| | FOR BOTH HOOD AND SUPPRESSION ARE REQUIRED PRIOR TO |
| | INSTALLATION. |
| | |
| | 17) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. OK ON |
| | SHEET E401. PLEASE ADD NOTE TO FIRE ALARM DRAWINGS. |
| | |
| | 18) FIRE DAMPERS TO BE TESTED FOR CLOSURE IN ACCORDANCE |
| | WITH UL 555 STANDARDS PRIOR TO FINAL INSPECTION. |
| | |
| | 19) FIRE ALARM SYSTEM SHALL BE UL CERTIFICATED FOR |
| | CENTRAL STATION SERVICE. CERTIFICATE REQUIRED AT TIME |
| | OF OR PRIOR TO FINAL FIRE ALARM INSPECTION. |
| | |
| | 20) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE |
| | ALARM SYSTEM IN ADDITION TO FIRE SPRINKLER SYSTEM. |
| | |
| | 21) SHEET LS-1 ILLUSTRATES AN EXIT SIGN IN EDUCATION |
| | ROOM 109 THAT IS NOT SHOWN ON SHEET EL-101. PLEASE |
| | CORRELATE INFORMATION. |
| | |
| | 22) SHEET LS-1 ILLUSTRATES AN EXIT SIGN IN SECOND FLOOR |
| | LOBBY THAT IS NOT SHOWN ON SHEET EL-102 LIGHTING PLAN. |
| | |
| | 23) THERE ARE NO SMOKE DETECTION DEVICES SHOWN IN |
| | ELECTRICAL ROOMS FIRST AND SECOND FLOORS ON FIRE ALARM |
| | PLANS. |
| | |
| | 24) FIRE ALARM DRAWINGS, SHEETS EF-101 AND EF-102 DON'T |
| | ILLUSTRATE TAMPER AND FLOW SWITCH EQUIPMENT EXCEPT FOR |
| | THE LEGEND. |
| | |
| | 25) ELEVATOR SHALL COMPLY WITH ASME A17.1. WARNING |
| | SIGNS REQUIRED IN ELEVATOR LOBBIES. |
| | |
| | 26) FIRE ALARM SYSTEM SHALL BE CLASS A OR FULLY |
| | ADDRESSABLE. |
| | |
| | 27) SHEET E-401 INDICATES DOOR HOLDERS, NOTE 10A BUT NO |
| | SUCH DEVICES ARE SHOWN ON FA SHEETS EF-101 AND EF-102. |
| | PLEASE CLARIFY. |
| | |
| | 28) SHEET FP-101 GENERAL NOTES 6,8 AND 11 REFERENCE PBC |
| | FIRE RESCUE. THE CORRECT AGENCY AND AHJ FOR REFERENCES |
| | PROJECT IS WEST PALM BEACH FIRE RESCUE. |
| | |
| | 29) IN ADDITION TO MULTI-PURPOSE FIRE EXTINGUISHERS, |
| | "K" TYPE EXTINGUISHER IS REQUIRED IN KITCHEN. |
| | |
| | 30) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | |
| | A RESPONSE LETTER INDICATING HOW AND WHERE ON THE PLANS |
| | EACH ITEM HAS BEEN ADDRESSED WOULD HELP EXPEDITE THE |
| | PLAN REVIEW PROCESS. |
| | |
| | |
| | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL |
| | FIRE PLAN REVIEW |
| | FIRE PREVENTION (561) 804-4756 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |