Plan Review Notes
Plan Review Notes For Permit 08050795
Permit Number 08050795
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-07-17 16:06:01***DENIED***
  
 1) PLEASE VERIFY CORRECT ADDRESS. PLANS INDICATE 814
 DIVISION AVE. AND PERMIT APPLICATION SHOWS 706 8TH ST.
  
 2) FIRE DEPARTMENT CONNECTION TO BE PROVIDED WITH KNOX
 LOCKING CAPS. CONTACT WEST PALM BEACH BUREAU OF FIRE
 PREVENTION AT (561( 804-4724 FOR APPLICATION.
  
 3) KNOX BOX REQUIRED ON BUILDING FOR AFTER NORMAL
 BUSINESS HOURS ACCESS FOR EMERGENCIES. CONTACT WEST
 PALM BEACH BUREAU OF FIRE PREVENTION AT (561) 804-4724
 FOR APPLICATION.
  
 4) IN ADDITION TO ELECTRONIC SUPERVISION, DOUBLE CHECK
 DETECTOR ASSEMBLY TO BE SECURED WITH LOCK AND CHAIN.
  
 5) PLEASE ADD NFPA 13, 2002 AND NFPA 72, 2002 TO
 BUILDING CODE ANALYSIS ON SHEET LS-1.
  
 6) PROVIDE CALCULATION FOR TOTAL BUILDING OCCUPANT LOAD
 USING NFPA 101, TABLE 7.3.1.2.
  
 7) CLARIFY DETECTION DEVICES SHOWN ON SHEET LS-1. ARE
 DEVICES AREA SMOKE DETECTORS OR DUCT SMOKE DETECTORS AS
 INDICATED IN LS SYMBOL LEGEND? NONE OF THESE DEVICES
 ARE INDICATED ON FIRE ALARM DRAWINGS.
  
 8) SMOKE DETECTORS NOT SHOWN IN AREA OF FACP OR
 ELEVATOR LOBBY FIRST FLOOR ON LS-1. OK ON FIRE ALARM
 PLANS. PLEASE CORRELATE INFORMATION.
  
 9) NO FIRE ALARM DEVICES ARE SHOWN IN MEETING ROOMS A
 AND B SECOND FLOOR ON SHEET LS-1.
  
 10) STAIR #2 SHOULD BE CORRECTED TO READ FIRE SPRINKLER
 RISER.
  
 11) PROVIDE MINIMUM STRENGTH REQUIREMENTS FOR GUARDS
 AND HANDRAILS.
  
 12) ADDRESS IS REQUIRED ON BUILDING THAT SHALL BE A
 MINIMUM OF 6" IN HEIGHT, 1" WIDTH AND CONTRASTING WITH
 BACKGROUND. PLEASE ADD TO ELEVATIONS.
  
 13) STAIRS TO COMPLY WITH NFPA 101 SEC. 7.2.2. PLEASE
 CLARIFY WIDTH OF TREADS.
  
 14) HANDRAILS ARE REQUIRED ON BOTH SIDES OF STAIRS.
 NFPA 101, SEC. 7.2.2.4.1.1.
  
 15) THE DOOR SCHEDULE INDICATES CLOSERS ON SOME OF THE
 DOORS. SOME OF THE RATED DOORS ARE LISTED WITH NO
 CLOSERS. PLEASE EXPLAIN OR ADD TO SCHEDULE.
  
 16) EQUIPMENT THAT COOKS FOOD CAPABLE OF PRODUCING
 GREASE LADEN VAPORS SHALL BE PROTECTED BY AN APPROVED
 HOOD/SUPPRESSION SYSTEM. THE SYSTEM SHALL BE TIED INTO
 THE FIRE ALARM AND SEPARATE SHOP DRAWINGS AND PERMITS
 FOR BOTH HOOD AND SUPPRESSION ARE REQUIRED PRIOR TO
 INSTALLATION.
  
 17) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS. OK ON
 SHEET E401. PLEASE ADD NOTE TO FIRE ALARM DRAWINGS.
  
 18) FIRE DAMPERS TO BE TESTED FOR CLOSURE IN ACCORDANCE
 WITH UL 555 STANDARDS PRIOR TO FINAL INSPECTION.
  
 19) FIRE ALARM SYSTEM SHALL BE UL CERTIFICATED FOR
 CENTRAL STATION SERVICE. CERTIFICATE REQUIRED AT TIME
 OF OR PRIOR TO FINAL FIRE ALARM INSPECTION.
  
 20) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 ALARM SYSTEM IN ADDITION TO FIRE SPRINKLER SYSTEM.
  
 21) SHEET LS-1 ILLUSTRATES AN EXIT SIGN IN EDUCATION
 ROOM 109 THAT IS NOT SHOWN ON SHEET EL-101. PLEASE
 CORRELATE INFORMATION.
  
 22) SHEET LS-1 ILLUSTRATES AN EXIT SIGN IN SECOND FLOOR
 LOBBY THAT IS NOT SHOWN ON SHEET EL-102 LIGHTING PLAN.
  
 23) THERE ARE NO SMOKE DETECTION DEVICES SHOWN IN
 ELECTRICAL ROOMS FIRST AND SECOND FLOORS ON FIRE ALARM
 PLANS.
  
 24) FIRE ALARM DRAWINGS, SHEETS EF-101 AND EF-102 DON'T
 ILLUSTRATE TAMPER AND FLOW SWITCH EQUIPMENT EXCEPT FOR
 THE LEGEND.
  
 25) ELEVATOR SHALL COMPLY WITH ASME A17.1. WARNING
 SIGNS REQUIRED IN ELEVATOR LOBBIES.
  
 26) FIRE ALARM SYSTEM SHALL BE CLASS A OR FULLY
 ADDRESSABLE.
  
 27) SHEET E-401 INDICATES DOOR HOLDERS, NOTE 10A BUT NO
 SUCH DEVICES ARE SHOWN ON FA SHEETS EF-101 AND EF-102.
 PLEASE CLARIFY.
  
 28) SHEET FP-101 GENERAL NOTES 6,8 AND 11 REFERENCE PBC
 FIRE RESCUE. THE CORRECT AGENCY AND AHJ FOR REFERENCES
 PROJECT IS WEST PALM BEACH FIRE RESCUE.
  
 29) IN ADDITION TO MULTI-PURPOSE FIRE EXTINGUISHERS,
 "K" TYPE EXTINGUISHER IS REQUIRED IN KITCHEN.
  
 30) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
  
 A RESPONSE LETTER INDICATING HOW AND WHERE ON THE PLANS
 EACH ITEM HAS BEEN ADDRESSED WOULD HELP EXPEDITE THE
 PLAN REVIEW PROCESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  