Plan Review Notes
Plan Review Notes For Permit 08050795
Permit Number 08050795
Review Stop E
Sequence Number 1
Notes
Date Text
2008-06-26 12:36:56** DENIEDREVIEW **
  
 *** IT IS IMPORTANT TO UNDERSTAND AS SOME THINGS HAVE
 NOT YET BEEN SUBMITTED FOR MINIMUM CODE COMPLIANCE
 THERE MAY VERY WELL BE NEW COMMENTS ON THE NEXT REVIEW
 WHICH CAN NOT BE MADE AT THIS TIME.
  
 1)NOTE: PLEASE SEE THE ADDRESS ON PLANS AND
 SUPPORTING DOCUMENTS ARE STATING 814 DIVISION AVE YET
 THE APPLIED LOCATION IS 706 8TH ST. PLEASE ADJUST TITLE
 BLOCKS ON ALL PLANS AND ALL SUPPORTING DOCUMENTS.
 FBC 106.5 ADMIN SECTION.
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE SEE THE SUBMITTED SURVEY IS REQUIRED TO
 CONTAIN AN ORIGINAL SIGNATURE. PER FS 472.025 MAY NOT
 PLACE RAISED SEAL OVER RUBBER STAMP SIGNATURE.
 STATEMENT PER FAC 61G17 AND AS STATED ON THE TITLE
 BLOCK FOR SAME SAID SHEETS STATE THE SHEET IS NOT VALID
 WITHOUT ORIGINAL SIGNATURE.
 PLEASE ADJUST. THIS IS A FLORIDA STATUTE AND REQUIRED
 WHETHER OR NOT COMMENT IS MADE BY ANY OTHER REVIEWER.
  
 3) NOTE: PLEASE SEE THE LANDSCAPE PLANS ARE MISSING THE
 REQUIRED CERTIFICATION OF AUTHORIZATION NUMBER AS
 REQUIRED PER FS 481.219, FAC 61G1-16.004.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE REVIEW.
  
 4) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS
 DO NOT CONTAIN ANY ORIGINAL SIGNATURES. IN FACT BOTH
 COPIES SUBMITTED CONTAIN A RAISED SEAL OVER A COLOR
 PHOTO-COPIED SIGNATURE BY THE ENGINEER. PLEASE SEE FAC
 61G15-23.002 AND FS 471.025 AS AN ORIGINAL SIGNATURE IS
 REQUIRED ON ALL DOCUMENTS DONE BY THE ENGINEER. THIS
 COMMENT HAS BEEN MADE BEFORE FOR THIS DESIGNER OF
 RECORD. PLEASE KNOW BOTH SETS OF CALCULATIONS SUBMITTED
 ARE BEING RETAINED BY THIS OFFICE.
  
 5) NOTE: PLEASE KNOW THE SUBMITTED ENERGY CALCULATIONS
 ARE NOT COMPLETE. NO INPUT DATA REPORT WAS SUBMITTED.
 PAGE TWO OF NINE STATES THE INPUT DATA REPORT MUST BE
 SUBMITTED ALONG WITH THE SUMMARY SHEETS. IN ANY CASE
 PLEASE KNOW THAT SOME OF THE INFORMATION ON THE
 SUBMITTED CALCULATIONS DOES NOT MATCH WITH THE PLANS.
 AN EXAMPLE OF THIS IS THE LIGHTING IN THE SUMMARY WHICH
 SHOWS A TOTAL OF 574 WATTS OF LIGHTING. HOW IS THIS
 POSSIBLE WHEN THE WSA FIXTURES ALONE EXCEED THE
 574WATTS? THERE ARE SEVERAL OTHER FIXTURES ON PLANS
 WHICH ARE NOT ACCOUNTED FOR.
 PLEASE BE SURE ALL INFORMATION ON THE INPUT DATA
 REPORTS COORDINATES WITH PLANS. PLEASE BE SURE ALL
 INTERIOR LIGHTING SUCH AS THE WATTAGE OF FIXTURES, THE
 TYPES OF FIXTURES, THE METHOD OF CONTROLS AND THE
 NUMBER OF FIXTURES. THIS OFFICE CAN NOT EMPHASIZE
 ENOUGH THAT ALL INFORMATION ON PLANS FOR ALL COMPONENTS
 OF THE BUILDING WILL NEED TO COORDINATE WITH THE
 SUBMITTED CALCULATIONS. ONE EXAMPLE ABOVE WAS GIVEN
 WITH RESPECT TO THE EXTERIOR LIGHTING EVEN AS SHOWN ON
 THE SUMMARY SHEETS DID NOT COORDINATE WITH THE
 SUBMITTED PLANS.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE 13-400.3.A AS SUBMITTED.
 ** PLEASE BE SURE TO SEE TRACK LIGHTING AS NOTED IN
 SECTIONS ABOVE.
 ** PLEASE BE SURE ALL LUMINAIRES SHOWN ON THE FIXTURE
 LEGEND AND ALL PLANS COORDINATE WITH THE TYPES. THERE
 WILL BE OTHER COMMENTS BELOW AS THERE ARE SEVERAL
 FIXTURES ON THE PLANS WHICH DO NOT APPEAR IN THE
 FIXTURE LEGEND.
 ** PLEASE BE SURE TO USE THE FIXTURE RATED OUTPUT
 WHETHER OR NOT IT IS INCANDESCENT, FLUORESCENT, OR HID
 ETC.
 ** PLEASE BE SURE TO SEE THE USE OF ANY LOW VOLTAGE
 SYSTEMS.
  
 6) NOTE: PLEASE SEE THE SUBMITTED CALCULATIONS STATE
 SCHOOL AS THE OCCUPANCY HOWEVER THE OCCUPANCY AS STATED
 BY THE ARCHITECT IS NOT EDUCATIONAL AND IN FACT IS
 STATED AS A3.
 PLEASE BE SURE THE *INDIVIDUAL* NOT THE FIRM IS LISTED
 AT THE PREPARER. THE CERTIFICATION SHEETS ARE SET UP
 FOR THE INDIVIDUAL CERTIFYING NOT A FIRM.
 PLEASE BE SURE TO ADJUST.
 13-415.2, 13-400.3.A, 13-103.1
  
 7) NOTE: PLEASE COORDINATE ALL ELECTRICAL PLANS. PLEASE
 SEE THE ELECTRICAL SITE PLANS SHOWN ON ES101 DO NOT
 MATCH WITH THE FIXTURES ETC ON ES102.
 PLEASE SEE OTHER SHEETS WHICH INDICATE SITE LIGHTING
 POLES YET THE ELECTRICAL SITE PLANS DO NOT INDICATE ANY
 SITE LIGHTING POLES.
 PLEASE SEE THE LUMINAIRE SCHEDULE ON ES 102 WHICH DOES
 NOT INCLUDE THE S32 FIXTURE AT ALL.
 PLEASE SEE TIME CLOCK SITE/EXTERIOR LIGHTING SCHEDULE
 WHICH ALSO INDICATES OTHER LIGHTING YET THE SITE PLANS
 ARE NOT COMPLETE AND DO NOT COORDINATE. THERE ARE
 SEVERAL ITEMS.
 NEC 220, 240,310,408 ETC
 FBC 13-415.2.ABC.1.3
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 8) NOTE: PLEASE BE SURE TO INDICATE THE REQUIRED
 ASTRONOMICAL TIME CLOCK AS REQUIRED PER
 13-415.1.ABC.1.4 WITH THE REQUIRED BACK UP OF
 PROGRAMMING.
  
 9) NOTE: PLEASE SEE THE TIME CLOCK SCHEDULE AS THE
 CIRCUITING SHOWN ON THIS SCHEDULE NEEDS TO COORDINATE
 WITH PLANS.
 PARKING LOT LTS, GAZEBO LTS ETC
 NEC 240, 220, 310.16
 FBC 13-415.2.ABC.1.3
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 10) NOTE: PLEASE SEE THERE ARE MISSING LIGHTING
 CONTROLS FOR 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE ONE EXAMPLE OF THIS IS THE STANDARD SINGLE
 POLE LIGHT SWITCH SHOWN FOR THE TRACK LIGHTS.
 THESE ARE ALSO REQUIRED TO BE CONTROLLED WITH SOME
 SORT OF AUTOMATED CONTROLS.
 ANOTHER EXAMPLE WOULD BE THE KITCHEN LIGHTING WHICH
 INDICATE STANDARD 3-WAY SWITCHES.
 ** SOME EXAMPLES ARE GIVEN ONLY. PLEASE BE SURE TO SEE
 OTHER COMMENTS WHICH MAY AFFECT LIGHTING AND CONTROLS.
 PLEASE BE SURE TO ADJUST SHOWING ALL MAXIMUM TIMES FOR
 ALL CONTROLS AND ALL DEVICES.
 MANY ARE OK, HOWEVER NOT ALL.
  
 11) NOTE: PLEASE SEE ANY ZONING COMMENTS WITH RESPECT
 TO THE AMOUNT OF LIGHTING PERMITTED OVER THE PROPERTY
 LINES. EVEN IF THERE HAVE BEEN NO COMMENTS FROM THE
 REVIEW PLEASE BE SURE TO CALL ZONING OFFICE TO VERIFY
 THE LIGHTING LEVELS OVER THE PROPERTY LINES. THIS IS
 NOTED FOR INFORMATION ONLY AND AS A BENEFIT SO THERE
 ARE NO ISSUES WITH FIXTURES AT A LATER DATE.
 SOME LEVELS APPEAR TO BE OVER THE ALLOWANCES IN SOME
 AREAS ONLY. THIS IS ONLY GIVEN FOR INFORMATION AND IS
 NOT AN ELECTRICAL REVIEW COMMENT WHICH NEEDS TO BE
 ADDRESSED. NO RESPONSE NEEDED.
  
 12) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL
 DESIGNATED EGRESS PATHS OUT FROM BUILDING. PLEASE BE
 SURE TO INCLUDE THE LIGHTING LEVELS UNDER NORMAL AND
 UNDER EMERGENCY CONDITIONS.
 PLEASE BE SURE TO SEENFPA-101 2003, 7.8.1.3 AND
 7.9.2.2 WHICH REQUIRES A MINIMUM OF 10FT CANDLESON
 ALL WALKING SURFACES OF STAIRS AND IS PERMITTED TO GO
 DOWN TO 1FT CANDLE UNDER EMERGENCY.
 PLEASE SEE 7.8.1.2.2 FOR TYPES OF OCCUPANCY SENSORS
 REQUIRED. THESE SHALL BE FAIL SAFE *ON*. THIS IS ALSO
 NOTED IN FBC 1016.1
  
 13) NOTE: AS NOTED ABOVE IN PREVIOUS NOTES WITH RESPECT
 TO FIXTURES AND COORDINATION AND NOTE #12 ABOVE PLEASE
 BE SURE TO COORDINATE ALL LIGHTING FIXTURES.
 PLEASE SEE MISSING SOME AS EXAMPLE: WS3E, B3E, WSA, TL1
 ETC
 PLEASE SEE FOR EXAMPLE MANY OF THE LIGHTING FIXTURES
 IN THE STAIRS AND OTHER LOCATIONS WHICH INDICATE AN *E*
 NEXT TO FIXTURE DESIGNATION. THIS FIXTURE IS NOT LISTED
 ON THE FIXTURE LEGEND WITH EMERGENCY BALLAST ETC.THE
 STAIR FIXTURES AND OTHER FIXTURES WHICH ARE ASSUMED TO
 CONTAIN BATTERY BACK UP BALLAST ARE IN NEED OF ALSO
 COORDINATING WITH THE PHOTO-METRICS TO BE SUBMITTED.
 NFPA-1017.8, 7.9
 FBC 13-415.2.ABC.1.1, .1.2
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 14) NOTE: PLEASE SEE THE MULTI-GANG BATHROOMS. THE
 PLANS INDICATE FOR LIGHTING CONTROLS A SINGLE POLE
 SWITCH DEVICE *AFTER* THEOCCUPANCY SENSING.
 PLEASE KNOW DUE TO THE LIFE SAFETY EGRESS SITUATION AS
 SHOWN THIS WOULD ALLOW AN OCCUPANT TO TURN OFF LIGHTING
 ON THE BATHROOMS WHILE AN OCCUPANT IS STILL IN ANY
 LOCATION THEREFORE LEAVING ANY ONE EGRESS AREA IN TOTAL
 DARKNESS.
 PLEASE ADJUST DESIGN SO THAT THIS DOES NOT OCCUR.
 NFPA-101 7.8, 13-415.1.ABC.1.2.
  
 15) NOTE: PLEASE SEE THAT MANY ROOMS AND AREAS OF THE
 PLANS HAVE DESIGNATIONS HOWEVER MANY AREAS OF THE PLANS
 IN FACT MOST ROOMS THE PRINT ON PLANS FOR THESE ROOMS
 AND AREAS ARE VERY FAINT AND NOT READABLE. THE REVIEW
 OF SEVERAL ITEMS FOR COORDINATION ON PLANS IS NEEDED
 AND PLEASE BE SURE TO ADJUST PRINT SO THESE CAN BE
 READ.
 FBC ADMIN SECTION 106.1, 106.1.1, 106.1.3 FOR CLARITY.
  
 16) NOTE: PLEASE PROVIDE DISCONNECTING MEANS AT GAZEBO
 PER 225.31-225.39
  
 17) NOTE: PLEASE PROVIDE THE REQUIRED GROUNDING
 ELECTRODE AT GAZEBO PER 250.32, 250.50 OR MEET THE
 EXCEPTION OF THE CODE.
  
 18) NOTE: PLEASE BE SURE TO COMPLETE ALL CIRCUITING ON
 PLANS. PLEASE SEE FOR EXAMPLE THE STAIRS WHICH NO
 CIRCUITING IS SHOWN.
 PLEASE SEE 700.12F.
 PLEASE SEE THERE ARE OTHER ITEMS ON PLANS AS WELL WHICH
 DO NOT INDICATE CIRCUITS AND/OR DO NOT CORRELATE WITH
 THE SUBMITTED PANEL SCHEDULES.
 PLEASE BE SURE TO COORDINATE ALL.
 NEC 240.4, 310.16, 220, 408.4
 FBC 106.1.2, 106.1.1, 106.3.5.1.2 FOR MINIMUM
 INFORMATION REQUIRED AND CLARITY.
  
 19) NOTE: PLEASE BE SURE TO SUBMIT MINIMUM WIND LOAD
 CALCULATIONS FOR LIGHT POLES. THE STRUCTURAL DESIGN
 REVIEW WILL BE DONE BY THE STRUCTURAL REVIEWER.
 THIS MAY BE DONE AS A PROVISO HOWEVER NEEDS BASIC
 DESIGN ON PLANS FOR OTHER TRADES.
 ** (SHOWS 140MPH ON ELECTRICAL ONLY)
  
 20) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE NEW PROPOSED MTS.
 NEC 110.3,90.7, 702.6
 FBC 106.1.2
  
 21) NOTE: PLEASE BE SURE THE MINIMUM LEVELS FOR HORNS,
 STROBES AND HORN/STROBES ARE ON PLANS FOR ADA
 COMPLIANCE PER FBC 11-4.28.1, .2 AND .3..
  
 22) NOTE: PLEASE SEE RISER WHICH SHOWS THE SERVICE MAIN
 DISCONNECT YET THE PLANS DO NOT SHOW THIS LOCATED ON
 THE OUTSIDE OF THE BUILDING ON SITE PLANS, POWER ETC.
 PLEASE BE SURE TO INCLUDE ON PLANS.
 230.70, 230.71, 230.72, 110.26, 240.24 ETC
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 23) NOTE: PLEASE SEE THE MAIN SERVICE DISCONNECT IS NOT
 RATED FOR THE SERVICE AS SHOWN. THE MAIN DISTRIBUTION
 PANEL IS SHOWN AS 1000AMPS, WITH A LOAD IN THE 900AMP
 RANGE YET THE SERVICE MAIN DISCONNECT IS SHOWN AT
 600AMPS.ALL EQUIPMENT SHALL BE RATED FOR THE LOAD
 SERVED.
 THIS IS NOT PERMITTED.
 230.70, 230.76, 230.79
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 24) NOTE: PLEASE SEE THE NOTE TO SEE THE GROUNDING
 ELECTRODE SYSTEM DETAILS FOR SERVICE NOTES TO SEE E201
 YET E201 DOES NOT CONTAIN ANY GROUNDING ELECTRODE
 SYSTEM DETAILS.
 ** CHECK SHEET NUMBERS.
  
 25) NOTE: PLEASE KNOW AS NOTED ABOVE FOR ENERGY
 CALCULATIONS. THE *FUTURE* LIGHT FIXTURE SHALL HAVE AN
 ASSUMPTION IN THE CALCULATIONS FOR ENERGY COMPLIANCE AS
 WELL AS ASSUMPTIONS IN THE LOAD CALCULATIONS.
 NEC 220.12, 220.42, FBC 13-415.2.ABC.1.1, .1.2 AND
 .1.3.
  
 26) NOTE:THE PLANS NOTES THE KITCHEN EQUIPMENT WILL
 NOT BE PART OF THE SCOPE HOWEVER WHAT ABOUT THE
 ELECTRICAL FOR WALLS ETC?
 PLEASE CLARIFY AS IF ANY RECEPTACLES ETC WILL BE
 INSTALLED BEFORE THE PROJECT IS ENDED MUST BE SHOWN IN
 CALCULATIONS, ON PLANS ETC.
 310.16, 240, 220, ETC
 FBC 106.1.1, 106.1.2, 106.3.5.1.2
  
 27) NOTE: PLEASE SEE 422.13 AS ANY STORAGE TYPE WATER
 HEATER IS CONSIDERED A*CONTINUOUS LOAD* UNDER THE 2005
 NEC. THIS REQUIRES THE LOAD TO BE SHOWN AND FIGURED AT
 125%.
  
 28) NOTE: PLEASE SEE THE PLANS ARE MISSING THE REQUIRED
 DEDICATE CIRCUITS FOR THE ELEVATOR EQUIPMENT ROOM. THE
 PLANS SHOW THE LIGHTING BEING CIRCUITED TO OTHER LIGHTS
 INSIDE THE BUILDING WHICH IS NOT PERMITTED PER
 620.23(A)(B).
 PLEASE ALSO INDICATE THAT THE MINIMUM LEVEL OF LIGHTING
 IN THE PIT MEETS THE 5FT CANDLES MINIMUM.
 ASME A17.1-2004, SAFETY CODE FOR ELEVATORS AND
 ESCALATORS, REQUIRES A MINIMUM OF 5 FT-CANDLES (54 LUX)
 AT THE PIT FLOOR AND REQUIRES LUMINAIRES TO BE
 EXTERNALLY GUARDED TO PREVENT ACCIDENTAL BREAKAGE.
  
 29) NOTE: PLEASE SEE FBC 3006.2 AS DEDICATE AIR
 CONDITIONING IS REQUIRED IN THE ELEVATOR EQUIPMENT
 ROOMS. THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE
 BY OTHER TRADE REVIEWERS.
  
 30) NOTE: PLEASE SEE 620.23C AS THE ELEVATOR EQUIPMENT
 ROOM IS ALSO MISSING THE REQUIRED DEDICATE GFI
 RECEPTACLE. THIS MAY BE ONE THE SAME CIRCUIT AS THE
 LIGHTS IN THIS ROOM.
  
 31) NOTE: AS NOTED ABOVE WITH RESPECT TO ALL FIXTURES
 ON PLANS NEEDING TO COORDINATE WITH THE FIXTURE LEGEND.
 THE LIGHT FIXTURE SHOWN ON THE LIGHTING PLANS INDICATES
 THE LIGHT AS AN *T2E* FIXTURE YET THE LEGEND DOES NOT
 INCLUDE THIS.
 PLEASE BE SURE THE FIXTURE IN THE ELEVATOR EQUIPMENT
 ROOM CONTAINS SOME SORT OF BATTERY BACK UP LIGHT
 FIXTURE AS WELL AS OTHER ELECTRICAL ROOMS. IT IS
 ASSUMED THE *E* ON THE PLANS IS FOR AN EMERGENCY BACK
 UP BALLAST HOWEVER CAN NOT CONFIRM.
 NEC 700.12F, 700.16, LS 101, 7.8, 7.9
  
 32) NOTE: PLEASE BE SURE TO COORDINATE THE ELECTRICAL
 CONDUITS SHOWN ON ES101 AS THESE ARE SHOWN TO GO FROM
 THE FPL TRANSFORMER TO THE INSIDE ELECTRICAL ROOM AND
 NOT TO THE MAIN DISCONNECT AS SHOWN ON RISER. THIS WAS
 ALSO NOTED ON NOTE #22ABOVE WITH RESPECT TO SHOWING
 LOCATION.
 230.70, 300.5 ETC
 FBC 106.1.1 FOR CLARITY.
  
 33) NOTE: PLEASE SEE PANEL 2LA WHICH SHOWS ON RISER A
 40AMP FEED YET THE PANEL BASED ON THE PANEL SCHEDULE
 AND BASED ON THE LOADS EXCEEDS THIS OVER CURRENT
 PROTECTION. LOAD IS 70 PLUS AMPS.
 PLEASE SEE THAT ALL EQUIPMENT SHALL BE RATED FOR LOAD
 SERVED.
 PLEASE ALSO SEE AS BASED ON RISER THESE ARE SHOWN AS
 1/0 CONDUCTORS ON A 40AMP BREAKER.
 THIS SEEMS TO BE A MISPRINT OF OVER CURRENT PROTECTION
 NEED
 240, 408, 310, ETC
 PLEASE BE SURE TO SEE MDP SCHEDULE AS BREAKER IS SHOWN
 AS 125AMPS.
 FBC 106.1.1 FOR COORDINATION AND CLARITY
  
 34) NOTE: PLEASE SEE MDP SHOWS A PANEL 1KA YET RISER
 DOES NOT SHOW ANY 1KA PANEL.
 PLEASE SEE RISER SHOWS A1LK, YET NOT LISTED ON THE
 MDP. ARE THESE PANELS THE SAME BUT MISLABLED?
 408.4
 FBC 106.1.1.
  
 35) NOTE: PLEASE VERIFY THE LINEAR FT SHOWN ON THE
 PANELS FOR VOLTAGE DROP. IT IS UNCLEAR HOW THE TVSS
 BREAKERS ARE SHOWING 10816FT, AND OTHERS SHOWS 1082 FT
 AND 541 FT.
 PLEASE BE SURE TO SEE FBC 13-413.1.ABC.1.1 AND .1.2 AND
 PROVIDE ACTUAL WORST CASE VOLTAGE DROP.
  
 36) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2. PLEASE
 PROVIDE THE WORDING AS STATED IN THE FBC ON PLANS IN
 NOTES.
 THIS WAS CONFIRMED ON A STATE LEVEL THE INTENT OF THE
 CODE IS FOR THE PLANS CONTAIN THE WORDING AS STATED IN
 THE SECTIONS.
  
 37) NOTE: PLEASE COMPLETE CIRCUITS ON DETAIL 2 ON
 E301.
 408.4, 240.4, 310.16ETC
 FBC 106.1.1
  
 38) NOTE: PLEASE SEE E402 WHICH STATES THE FPL
 TRANSFORMER AS 225KVA YET THE SITE PLAN SHOWS 100KVA.
 PLEASE COORDINATE.
 FBC 106.1.1 FOR CLARITY OF PLANS.
  
 39) NOTE: PLEASE SEE THE ELEVATORCAB LIGHTS WHICH
 SHOWS 2-#8 AWG ON A 1-POLE 20AMP BREAKER. HOW IS THIS
 POSSIBLE?
 PLEASE SEE 430, 310.16, 240.4 ETC 110.3.
  
 40) NOTE: PLEASE SEE THE RISER AS THIS SHOWS A 125AMP
 BREAKER/OVER CURRENT PROTECTION FEEDING A 100AMP RATED
 DISCONNECT.
 110.3, 90.7 ETC
 FBC 106.1.1 FOR CLARITY.
  
 41) NOTE: PLEASE SEE RISER NOTES THE CONTRACTOR IS
 RESPONSIBLE TO OBTAIN THE ACTUAL AVAILABLE FAULT
 CURRENT AND MAKE ADJUSTMENTS.
 PLEASE KNOW THIS IS THE RESPONSIBILITY OF THE DESIGNER
 OF THE ELECTRICAL SYSTEM NOT THE CONTRACTOR FOR BASE
 DESIGN. THE CONTRACTOR MOST CERTAINLY WILL NEED TO
 VERIFY THE TRANSFORMER ETC FROM THE UTILITY IS
 INSTALLED BASED ON INFORMATION FROM THE UTILITY. ANY
 CHANGE IN THE ACTUAL SIZE, AND IMPEDANCE RATING OF THE
 UNIT WILL NEED TO BE GIVEN TO THE ENGINEER IN CASE ANY
 EQUIPMENT NEEDS TO BE ADJUSTED.
 PLEASE SEE 110.9 AND ADJUST NOTES.
 FAC 61G15-33.001, .003 FOR THE ENGINEER.
  
  
 42) NOTE: BASED ON THE TYPE OF COMMENTS AND THE AMOUNT
 OF COMMENTS ABOVE ONE SET OF ELECTRICAL PLANS ALONG
 WITH THE PARTIAL ENERGY CALCULATIONS MAY BE RETAINED BY
 THIS OFFICE.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]